Installation EDUS39-600-F1_aFXFQ-M 3412. FIELD SETTINGMake sure the terminal box lids are closed on the indoorand outdoor units.Field setting must be made from the remote controller inaccordance with the installation condition.• Setting can be made by changing the MODE NO., , FIRSTCODE NO., and SECOND CODE NO.• For setting and operation, refer to the FIELD SETTING inthe installation manual of the remote controller• Set the remote controller to the field set mode. Fordetails, refer to HOW TO SET IN THE FIELD in theremote controller manual.• When in the field set mode, select mode No. 12, thenset the first code (switch) No. to [1]. Then set secondcode (position) No. to [01] for FORCED OFF and [02]for ON/OFF OPERATION. (FORCED OFF is factorysetting.)13. INSTALLATION OF THE DECORATIONPANELRefer to the installation manual attached to the decorationpanel.After installing the decoration panel, ensure that there is nospace between the unit body and decoration panel.14. TEST OPERATIONRefer to the installation manual of the outdoor unit.• The operation lamp of the remote controller will flash whena malfunction occurs. Check the malfunction code on theliquid crystal display to identify the point of trouble. Anexplanation of malfunction codes and the correspondingtrouble is provided in CAUTION FOR SERVICING of theoutdoor unit.If any of the items in Table 6 are displayed, there may be aproblem with the wiring or power, so check the wiring again.Table 6