• VRV Systems ® • Indoor Units 5• Indoor Units • ROUNDFLOW CASSETTE • FXFQ-P7VEB1 Specifications1-2 ELECTRICAL SPECIFICATIONS FXFQ20P7VEB FXFQ25P7VEB FXFQ32P7VEB FXFQ40P7VEB FXFQ50P7VEBPower Supply Name VEFrequency Hz 50/60Voltage V 220-240/220Current Minimum circuit amps(MCA)A 0.4 0.4 0.4 0.5 0.6Maximum fuse amps (MFA) A 16 16 16 16 16Full load amps (FLA) A 0.3 0.3 0.3 0.4 0.5Voltage range Minimum V -10%Maximum V +10%Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not belowor above listed range limits.Maximum allowable voltage range variation between phases is 2%.MCA/MFA : MCA = 1.25 x FLAMFA <= 4 x FLAnext lower standard fuse rating minimum 16Aselect wire size based on the MCAinstead of a fuse, use a circuit breaker1-2 ELECTRICAL SPECIFICATIONS FXFQ63P7VEB FXFQ80P7VEB FXFQ100P7VEB FXFQ125P7VEBPower Supply Name VEFrequency Hz 50/60Voltage V 220-240/220Current Minimum circuit amps(MCA)A 0.9 0.9 1.4 1.9Maximum fuse amps (MFA) A 16 16 16 16Full load amps (FLA) A 0.7 0.7 1.1 1.5Voltage range Minimum V -10%Maximum V +10%Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not belowor above listed range limits.Maximum allowable voltage range variation between phases is 2%.MCA/MFA : MCA = 1.25 x FLAMFA <= 4 x FLAnext lower standard fuse rating minimum 16Aselect wire size based on the MCAinstead of a fuse, use a circuit breaker