311• VRV ® Systems • Indoor Units 3• Indoor Units • Round Flow Cassette • FXFQ-PVE91 Specifications1-2 ELECTRICAL SPECIFICATIONS (50HZ) FXFQ25PVE9 FXFQ32PVE9 FXFQ40PVE9 FXFQ50PVE9 FXFQ63PVE9 FXFQ80PVE9 FXFQ100PVE9 FXFQ125PVE9Power Supply Name VEPhase 1~Frequency Hz 50Voltage V 220-240Current Minimum circuit amps (MCA) A 0.3 0.3 0.3 0.3 0.4 0.5 1.3 1.5Maximum fuse amps (MFA) A 15 15 15 15 15 15 15 15Full load amps (FLA) A 0.2 0.2 0.2 0.2 0.3 0.4 1.0 1.2Voltage range Minimum V -10%Maximum V +10%Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminalsis not below or above listed range limits.Maximum allowable voltage range variation between phases is 2%.MCA/MFA : MCA = 1.25 x FLAMFA is smaller than or equal to 4 x FLANext lower standard fuse rating minimum 15ASelect wire size based on the MCAInstead of a fuse, use a circuit breaker1-3 ELECTRICAL SPECIFICATIONS (60HZ) FXFQ25PVE9 FXFQ32PVE9 FXFQ40PVE9 FXFQ50PVE9 FXFQ63PVE9 FXFQ80PVE9 FXFQ100PVE9 FXFQ125PVE9Power Supply Name VEPhase 1~Frequency Hz 60Voltage V 220Current Minimum circuit amps (MCA) A 0.3 0.3 0.3 0.3 0.4 0.5 1.3 1.5Maximum fuse amps (MFA) A 15 15 15 15 15 15 15 15Full load amps (FLA) A 0.2 0.2 0.2 0.2 0.3 0.4 1.0 1.2Voltage range Minimum V -10%Maximum V +10%Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminalsis not below or above listed range limits.Maximum allowable voltage range variation between phases is 2%.MCA/MFA : MCA = 1.25 x FLAMFA is smaller than or equal to 4 x FLANext lower standard fuse rating minimum 15ASelect wire size based on the MCAInstead of a fuse, use a circuit breaker