• VRV ® Systems • Indoor Units 8• Indoor Units • Ceiling Suspended Unit • FXHQ-MAVE6 Dimensional drawing & centre of gravity6 - 1 Dimensional drawing316FXHQ32MA3D038855Hanging bolt4 - M8~M1030 or more(Service space)30 or more(Service space)(Hanging position)The front Brand name plate(Note 2)Drain pipe connection VP20(For left piping)Position slit hole for taking out in piping backPosition: hole of wallfor taking out in piping back(View from the front)(Required space)(Hanging position)(Required space)(Required space)300 or moreFor height installationFrom the floor side 2500 or moreFloor sideObstacle(View from the front)NOTES1 Location of unit’s name plate: bottom of fan housing inside the suctiongrille.2 In case of using infrared remote control, this position will be a signalreceiver. Refer to the drawing of infrared remote control, in detail.3 The remote control code is standard (about 3m outside the machine)attached. (0.5mm 2 x 2 wicks x O.D. ø 5.4) (It is not attached to VRV)Nr Part name Description1 Air discharge grille2 Air suction grille3 Air filter4 Gas pipe connection ø 12.7 flare5 Liquid pipe connection ø 6.4 flare6 Drain pipe connection VP207 Earth terminal (inside the electric components box) M48 Suspension bracket9 Backward piping and wiring connection opening lid10 Upward piping and wiring connectiojn opening lid11 Right side pipe connection Slit hole12 Left back drain pipe connection Slit hole13 Left side drain pipe connection Slit hole14 Right side drain pipe connection Slit hole15 Hole of wall for taking out in piping back ø 10016 Upward drain pipe connection ø 6017 Upward gas pipe connection ø 3618 Upward liquid pipe connection ø 26FXHQ63MA3D038856Hanging bolt4 - M8~M1030 or more(Service space)30 or more(Service space)(Hanging position)The frontBrand name plate(Note 2)Drain pipe connection VP20(For left piping)Position slit hole for taking out in piping back(View from the front)Position: hole of wallfor taking out in piping back(View from the front)(Required space)(Hanging position)(Required space)(Required space)300 or moreFor height installationFrom the floor side 2500 or moreFloor sideObstacleNOTES1 Location of unit’s name plate: bottom of fan housing inside thesuction grille.2 In case of using infrared remote control, this position will be a signalreceiver. Refer to the drawing of infrared remote control, in detail.3 The remote control code is standard (about 3m outside themachine) attached. (0.5mm 2 x 2 wicks x O.D. ø 5.4) (It is notattached to VRV)Nr Part name Description1 Air discharge grille2 Air suction grille3 Air filter4 Gas pipe connection ø 15.9 flare5 Liquid pipe connection ø 9.5 flare6 Drain pipe connection VP207 Earth terminal (inside the electric components box) M48 Suspension bracket9 Backward piping and wiring connection opening lid10 Upward piping and wiring connection opening lid11 Right side pipe connection Slit hole12 Left back drain pipe connection Slit hole13 Left side drain pipe connection Slit hole14 Right side drain pipe connection Slit hole15 Hole of wall for taking out in piping back ø 10016 Upward drain pipe connection ø 6017 Upward gas pipe connection ø 3618 Upward liquid pipe connection ø 26