9EnglishSummary of field settingsModeNo.(Note 1)FirstcodeNo.Description of settingSecond code No. (Note 2)01 02 03 0410(20)0Filtercontamination -Heavy/Light= Setting todefine timebetween 2 filtercleaning displayindications.(Whencontaminationis high, settingcan be changedto half the timein-between 2 filtercleaning displayindications.)LongLifeFilterLight±2,500 hrs.Heavy±1,250 hrs. — —2 Thermostat sensorselectionUse both theunit sensor(or remotesensor ifinstalled) ANDthe remotecontrollersensor.(See note 4+5)Use unitsensor only(or remotesensor ifinstalled).(See note4+5)Useremotecontrollersensoronly.(See note4+5)—3“Time to clean filter”displayed or notdisplayedDisplay Do notdisplay — —5Information toI-manager,I-touch controllerOnly unitsensorvalue (orremotesensorvalue ifinstalled).Sensorvalue as setby 10-2-0Xor 10-6-0X.— —6 Thermostat sensor ingroup controlUse unitsensor only(or remotesensor ifinstalled).(See note 5)Use both theunit sensor(or remotesensor ifinstalled) ANDthe remotecontrollersensor. (Seenote 3+4+5)— —12(22)0Output signal X1-X2 of the optionalKRP1B PCB kitThermostat-on +compressor run — Operation Malfunction1ON/OFF input from outside(T1/T2 input) = Settingwhen forced ON/OFF is tobe operated from outside.Forced OFF ON/OFFoperation — —2Thermostatdifferentialchangeover = Settingwhen remote sensoris used.1.8°F(1°C)0.9°F(0.5°C) — —3Fan setting duringthermostat OFF atheating operationLL Set speed — —4 Differential automaticchangeover0°F(0°C)1.8°F(1°C)3.6°F(2°C)5.4°F(3°C)(Seenote 6)5 Auto-restart afterpower failure Disabled Enabled — —6Fan setting duringthermostat OFF atcooling operationLL Set speed — —13(23)0Setting for air outletvelocityThis setting is to bechanged in functionof ceiling height.≤8 to 3/4 ft.(2.7 m orless)8-3/4 to 10(2.7-3.0)10 to11-1/2(3.0-3.5)—1Selection for air flowdirectionThis setting is tobe changed whenblocking pad optionalkit is used.4-way flow 3-way flow 2-wayflow —4Airflow directionrange settingThis setting is to bechanged when rangeof horizontal blademovement needs tobe changed.Upper Medium Lower —Note 1: Setting is carried out in the group mode, however, if the modenumber inside parentheses is selected, indoor units can alsobe set individually.Note 2: Factory settings of the Second code No. are marked in greybackground.Note 3: If group control is selected and remote controller sensor is tobe used, then set 10-6-02 & 10-2-03.Note 4: If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set atthe same time, then setting 10-2-01, 10-2-02 or 10-2-03 havepriority.Note 5: If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set atthe same time, then setting for group connection, 10-6-01 haspriority and for individual connection, 10-2-01, 10-2-02 or10-2-03 have priority.Note 6: More settings for Differential automatic change overtemperatures are:Second code No. 05 7.2°F (4°C)06 9.0°F (5°C)07 10.8°F (6°C)08 12.6°F (7°C) When using wireless remote controllers it is necessary to useaddress setting. Refer to the installation manual attached to thewireless remote controller for the setting instructions.