Si39-302 Troubleshooting by Indication on the Remote ControllerTroubleshooting 1812.21 ìF6î Refrigerant OverchargedRemoteControllerDisplayF6ApplicableModelsRXYQ5~48MMethod ofMalfunctionDetectionRefrigerant overcharge is detected from the receiver gas pipe temperature during testoperation.MalfunctionDecisionConditionsWhen the receiver gas pipe temperature is lower than evaporating temperature during testoperation.SupposedCauses! Refrigerant overcharge! Disconnection of the receiver gas pipe thermistorTroubleshooting(V2797)CautionBe sure to turn off power switch before connect or disconnect connector,or parts damage may be occurred.Is thereceiver gas pipetemperature thermistorinstalled the gas reliefpipe on top ofreceiver?Is thecharacteristic of thereceiver gas pipethermistornormal?Refrigerant overcharged.YESNONOReplace thermistor.Install thermistor correctly.YES