Si39-302 Troubleshooting by Indication on the Remote ControllerTroubleshooting 2012.40 ìU2î Power Supply Insufficient or Instantaneous FailureRemoteControllerDisplayU2ApplicableModelsRXYQ5~48MMethod ofMalfunctionDetectionDetection of voltage of main circuit capacitor built in the inverter and power supply voltage.MalfunctionDecisionConditionsSupposedCauses! Power supply insufficient! Instantaneous failure! Open phase! Defect of inverter PC board! Defect of outdoor control PC board! Defect of K1M.! Main circuit wiring defect