Specifications SiBE34-80222 SpecificationsCeiling Suspended Type1-1 TECHNICAL SPECIFICATIONS FXHQ32MAVE FXHQ63MAVE FXHQ100MAVENominalCapacityCooling kW 3.60 7.10 11.20Heating kW 4.00 8.00 12.50Power input(Nominal)Cooling kW 0.111 0.115 0.135Heating kW 0.111 0.115 0.135Casing Colour White (10Y9/0,5)Dimensions UnitHeight mm 195 195 195Width mm 960 1160 1400Depth mm 680 680 680Weight Unit kg 24 28 33HeatExchanger DimensionsNr of Rows 2 3 3Fin Pitch mm 1.75 1.75 1.75Face Area m² 0.182 0.233 0.293Nr of Stages 12 12 12Fan Type Sirocco fanQuantity 1 1 1Air Flow Rate Cooling High m³/min 12.00 17.50 25.00Low m³/min 10.00 14.00 19.50Fan MotorQuantity 1 1 1Model 3D12K1AA1 4D12K1AA1 3D12K2AA1Output(high) W 62 62 130Drive Direct driveRefrigerant Name R-410ACooling SoundPressureHigh dBA 36.0 39.0 45.0Low dBA 31.0 34.0 37.0PipingconnectionsLiquid (OD) Type Flare connectionDiameter mm 6.4 9.5 9.5Gas Type Flare connectionDiameter mm 12.7 15.9 15.9Drain Diameter mm 26 26 26Heat Insulation Glass woolAir Filter Resin net with mold resistanceRefrigerant control Electronic expansion valveTemperature control Microprocessor thermostat for cooling and heatingSafety devices PC board fuse, Fan motor thermal protectorStandard Accessories Installation and operation manual, Drain hose, Paper pattern for installation, Clamp metal, Insulation for fittingClamps, WasherNotesNominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,equivalent refrigerant piping : 7,5m (horizontal)Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,equivalent refrigerant piping : 7.5m (horizontal)Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.