SiBE34-802 Field SettingTest Operation 873. Field Setting3.1 Field Setting from Remote ControllerIndividual function of indoor unit can be changed from the remote controller. At the time ofinstallation or after service inspection / repair, make the local setting in accordance with thefollowing description.Wrong setting may cause malfunction.(When optional accessory is mounted on the indoor unit, setting for the indoor unit may berequired to change. Refer to information in the option handbook.)3.1.1 Wired Remote ControllerBRC1C621. When in the normal mode, press the “ ” button for a minimum of four seconds, and theFIELD SET MODE is entered.2. Select the desired MODE NO. with the “ ” button ().3. During group control, when setting by each indoor unit (mode No. 20, 22 and 23 have beenselected), push the “ ” button () and select the INDOOR UNIT NO to be set. (Thisoperation is unnecessary when setting by group.)4. Push the “ ” upper button () and select FIRST CODE NO.5. Push the “ ” lower button () and select the SECOND CODE NO.6. Push the “ ” button () once and the present settings are SET.7. Push the “ ” button () to return to the NORMAL MODE.(Example)If during group setting and the time to clean air filter is set to FILTER CONTAMINATION,HEAVY, SET MODE NO. to “10” FIRST CODE NO. to “0”, and SECOND CODE NO. to “02”.SETTINGTESTUNIT NO.3 456712FIELDSETMODEUNIT NO..SECONDCODE NO..MODE NO.FIRSTCODE NO..(V0292)