32• Split - Sky Air • RZAG-LV1 3• Outdoor Unit • RZAG-LV12 Specifications2-1 Capacity and Power input FCAHG71F/RZAG71LV1FCAHG100F/RZAG100LV1FCAHG125F/RZAG125LV1FCAHG140F/RZAG140LV1Cooling capacity Nom. kW 6.8 9.5 12.0 13.4Heating capacity Nom. kW 7.5 10.8 13.5 15.5Power input Cooling Nom. kW 1.66 2.15 3.00 4.00Heating Nom. kW 1.56 2.16 3.07 3.77Seasonal efficiency(according toEN14825)Cooling Energy label A++ -Pdesign kW 6.80 9.50 12.00 -SEER 7.35 (1) 6.94 (1) -Annual energyconsumptionkWh 324 452 605 -ACondition(35°C -27/19)Pdc kW 6.80 9.50 12.00 -EERd 4.38 4.61 4.10 -powerinputkW 1.55 2.06 2.93 -BCondition(30°C -27/19)Pdc kW 5.01 7.00 8.90 -EERd 6.12 5.95 5.40 -powerinputkW 0.82 1.18 1.65 -CCondition(25°C -27/19)Pdc kW 3.57 4.70 5.80 -EERd 9.30 8.25 8.40 -powerinputkW 0.38 0.57 0.69 -DCondition(20°C -27/19)Pdc kW 3.38 3.60 2.60 -EERd 12.10 13.15 9.80 -powerinputkW 0.28 0.27 -Heating (Averageclimate)Energy label A+ A++ -Pdesign kW 5.65 9.13 9.52 -SCOP/A 4.54 (1) 4.64 (1) 4.63 (1) -SCOPnet/A 4.55 4.67 4.64 -Pdh Heating capacity at -10° 5 8 9 -Annual energyconsumptionkWh 1,743 2,753 2,879 -Required back upheating cap at designconditionskW 0.21 0.86 0.21 -TOL Tol(temperatureoperatinglimit)°C -15 -Pdh(declaredheatingcap)kW 6.19 8.60 10.80 -COPd (declaredCOP)2.05 2.11 1.87 -PowerinputkW 3.02 4.07 5.78 -