• Outdoor Unit • RZAG-LV12• Split - Sky Air • RZAG-LV162 SpecificationsStandard Accessories : Tie-wraps; Quantity : 2;Standard Accessories : Installation manual; Quantity : 1;Refrigerant Type R-32Charge kg 2.6 3.4TCO 2 eq 1.8 2.3Control Expansion valve (electronic type)GWP 675Circuits Quantity 1Piping connections Liquid Quantity 1Type Flare connectionOD mm 9.52Gas Quantity 1Type Flare connectionOD mm 15.9Drain Quantity 5Type HoleID mm -OD mm 26.0Piping length OU - IU Min. m 3Max. m 55 85System Equivalentm 75 100Chargelessm 30Additional refrigerant charge kg/m See installation manualLevel difference IU - OU Max. m 30.0IU - IU Max. m 0.5Heat insulation Both liquid and gas pipesRefrigerant oil Type FW68DACharged volume l 0.9 1.35Defrost method Reversed cycleDefrost control Sensor for outdoor heat exchanger temperatureSafety devices Item 01 High pressure switch02 Low pressure switch03 Fan driver overload protector04 Fuse2-3 Electrical Specifications RZAG71LV1 RZAG100LV1 RZAG125LV1 RZAG140LV1Power supply Name V1Phase 1~Frequency Hz 50/60Voltage V 220-240Voltage range Min. % 198Max. % 264Current - 50Hz Maximum fuse amps (MFA) A -Current Zmax List Complies to EN61000-3-11Minimum Ssc value kVa Equipment complying with EN / IEC 61000-3-12Recommended fuses A 20 32Current - 60Hz Maximum fuse amps (MFA) A -Wiring connections For power supply Remark See installation manual outdoor unitFor connection withindoorRemark See installation manual outdoor unitPower supply intake Outdoor unit only2-2 Technical Specifications RZAG71LV1 RZAG100LV1 RZAG125LV1 RZAG140LV1