ESIE15-13C Field Setting from Remote ControllerField Setting 672.3 Settings Contents and Code No. for Indoor Units You can change the setting of 3 x 3 sensing cassette as mentioned below The method of field setting, which can be conducted through remote controller, isestablished practice, but it is possible only with BRCE52 remote controller.ModeNo.FirstCodeNo. Description of Setting Second Code No.01 02 03 04 0510(20)0FiltercleaningsignintervalLong lifefilter 2,500 hrs. 1,250 hrs. — — —1 Filter type Long Super long — — —2 Remote controllerthermistor Enabled Disabled — — —3 Filter cleaning sign Display No display — — —7(note 4) Detection time for NOTpresence 30 min 60 min — — —8(note 5)Compensation ofsuction air temperaturein heating modeCOMPENSATE(Temperature[A+2] °C which anair conditionercontrols when thetemperature of aremote controlleris A °C)NOCOMPENSATION(Temperature [A]°C which an airconditionercontrols when thetemperature of aremote controlleris A °C)— — —11(21)2 Fan OFF at ThermostatOFF Normal OFF — — —3 Airflow rate settingduring heating Standard Slightly up Up — —4 Automatic operationmode control Available Prohibition — — —6(note 6) Sensitivity of presencesensor High Low Standard Sensor doesnot work —11(22)0 Option (KRP1B*) output Compressor Option Operation Malfunction —7(note 6)Compensation oftemperature aroundhuman bodyFloor sensor doesnot workHigher priority onthe airtemperature StandardHigherpriority onthe floortemperature—8(note 6) Compensation of floortemperature -4°C -2°C ±0°C +2°C —12(22)3 Fan speed heatingthermostat OFF LL-speed Set-speed — —5 Automatic restart afterpower failure reset Disabled Enabled — —6 Fan speed coolingthermostat OFF LL-speed Set-speed — —13(23)0 High air outlet velocity(for high ceilingapplications) Standard Slightly up Up —1 Selection of airflowdirection 4-way flow 3-way flow — —2 Flap moving in theswing mode All 4 flapssynchronized — Two oppositeflapssynchronized — —4 (*2) Airflow range setting Upper Normal Lower —