32• Split - Sky Air • RZQSG-L(8)Y1 7• Outdoor Unit • RZQSG-L(8)Y12 SpecificationsSound pressure level Cooling Nom. dBA 53 54 53Heating Nom. dBA 57 58 54Night quiet mode Level 1 dBA 49Operation range Cooling AmbientMin. °CDB -15Max. °CDB 46Heating AmbientMin. °CWB -15Max. °CWB 15.5Refrigerant Type R-410ACharge kg 2.9 4.0TCO 2 eq 6.1 8.4Control Expansion valve (electronic type)GWP 2,087.5Circuits Quantity 1Refrigerant oil Type FVC50KCharged volume l 0.9 1.35Piping connections Liquid Quantity 1Type Flare connectionOD mm 9.52Gas Quantity 1Type Flare connectionOD mm 15.9Drain Quantity 5Type HoleID mm -OD mm 26Piping length OU - IU Min. m 5Max. m 50System Equivalentm 70Chargelessm 30Additional refrigerant charge kg/m See installation manualLevel difference IU - OU Max. m 30IU - IU Max. m 0.5Heat insulation Both liquid and gas pipesDefrost method Reversed cycleDefrost control Sensor for outdoor heat exchanger temperatureSafety devices Item 01 High pressure switch02 Fan driver overload protector03 Fuse2-9 Electrical Specifications RZQSG100L8Y1 RZQSG125L8Y1 RZQSG140LY1Power supply Name Y1Phase 3N~Frequency Hz 50Voltage V 380-415Voltage range Min. % -10Max. % 10Current Zmax List Complies to EN61000-3-11A Recommendedfuses20Current - 50Hz Maximum fuse amps (MFA) A 20Current - 60Hz Maximum fuse amps (MFA) A -Wiring connections For power supply Remark See installation manual outdoor unitFor connection withindoorRemark See installation manual outdoor unitPower supply intake Outdoor unit only2-8 Technical Specifications RZQSG100L8Y1 RZQSG125L8Y1 RZQSG140LY1