SiE33-102 InstallationGeneral Information 59Selection ofLocationWhen placing several units in close proximity to each other some thought should be given to the possibilityof short circuiting and also to the provision of adequate space for servicing. (For more detailed informationplease refer to the system design materials.)This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrialenvironment. If installed as a household appliance it could cause electromagnetic interference.The VRV plus outdoor units should be installed in a location that meets the following requirements:1. The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibrationand noise generation.2. The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet isavailable. (Refer to figure 1 and choose one of both possibilities.)3. There is no danger of fire due to leakage of inflammable gas.4. Ensure that water cannot cause any damage to the location in case it drips out the unit (e.g. in case ofa blocked drain pipe).5. The piping length between the outdoor unit and the indoor unit may not exceed the allowable pipinglength. (See “Example of connection”.)6. Select the location of the unit in such a way that neither the discharged air nor the sound generated bythe unit disturb anyone.7. Make sure that the air inlet and outlet of the unit are not positioned towards the main wind direction.Frontal wind will disturb the operation of the unit. If necessary, use a windscreen to block the wind.Caution 1. An inverter air conditioner may cause electronic noise generated from AM broadcasting. Examinewhere to install the main air conditioner and electric wires, keeping proper distances away from stereoequipment, personal computers, etc.If the electric wave of AM broadcasting is particularly weak, keep distances of 3m or more and useconduit tubes for power and transmission lines.2. In heavy snowfall areas, select an installation site where snow will not affect operation of the unit.3. The refrigerant R-22 itself is nontoxic, nonflammable and is safe. If the refrigerant should leak however,its concentration may exceed the allowable limit depending on room size. Due to this it could benecessary to take measures against leakage. Refer to the chapter 'Caution for refrigerant leaks'.RSXY16,18,20KAFront sideFront side≥50≥100≥10B1B2A≥20≥500≥10≥50RSXY24,26,28,30KAFront sideFront side≥50 ≥50≥10≥100≥20≥500 B1AB2≥10H ≤ 1500 ⇒ A ≥ 500h ≤ 500 ⇒ B1 ≥ 300H = 1500+X ⇒ A ≥ 500+X/2h = 500+Y ⇒ B1 ≥ 300+Y/2H ≤ 1500 ⇒ A ≥ 500h ≤ 500 ⇒ B2 ≥ 100H = 1500+X ⇒ A ≥ 500+X/2h = 500+Y ⇒ B2 ≥ 100+Y/2hHAB1B2(mm)Fig. 1(V1880)1. Personal Computer or Radio2. Fuse3. Earth Leak Detector4. Remote Control5. Cool/Heat Selector6. Indoor Unit≥1500135422(mm)63≥1000≥1000≥1000≥1500≥1500≥1500Fig. 2(V0850)Si33-102.book Page 59 Tuesday, June 26, 2001 3:18 PMВсе каталоги и инструкции здесь: http://splitoff.ru/tehn-doc.html