6 Application Set-Up Examples6.1 IntroductionNOTEWhen the optional safe stop feature is used, a jumper wiremay be required between terminal 12 (or 13) and terminal37 for the frequency converter to operate when usingfactory default programming values.The examples in this section are intended as a quickreference for common applications.• Parameter settings are the regional default valuesunless otherwise indicated (selected in0-03 Regional Settings)• Parameters associated with the terminals andtheir settings are shown next to the drawings• Where switch settings for analog terminals A53 orA54 are required, these are also shown6.2 Application ExamplesParametersFC+24 V+24 VD IND IND INCOMD IND IND IND IN+10 VA INA INCOMA OUTCOM12131819202729323337505354554239130BB929.10Function Setting1-29 AutomaticMotorAdaptation(AMA)[1] EnablecompleteAMA5-12 Terminal 27Digital Input[2]* Coastinverse* = Default ValueNotes/comments: Parametergroup 1-2* must be setaccording to motorD IN 37 is an option.Table 6.1 AMA with T27 ConnectedParametersFC+24 V+24 VD IND IND INCOMD IND IND IND IN+10 VA INA INCOMA OUTCOM12131819202729323337505354554239130BB930.10Function Setting1-29 AutomaticMotorAdaptation(AMA)[1] EnablecompleteAMA5-12 Terminal 27Digital Input[0] Nooperation* = Default ValueNotes/comments:Parameter group 1-2* must beset according to motorD IN 37 is an option.Table 6.2 AMA without T27 ConnectedParametersFC+24 V+24 VD IND IND INCOMD IND IND IND IN+10 VA INA INCOMA OUTCOM12131819202729323337505354554239A53U - I-10 - +10V+-130BB926.10Function Setting6-10 Terminal 53Low Voltage 0.07 V*6-11 Terminal 53High Voltage10 V*6-14 Terminal 53Low Ref./Feedb.Value0 Hz6-15 Terminal 53High Ref./Feedb.Value50 Hz* = Default ValueNotes/comments:D IN 37 is an option.Table 6.3 Analog Speed Reference (Voltage)Application Set-Up Examples VLT® HVAC Drive Operating InstructionsMG11AI02 - VLT® is a registered Danfoss trademark 476 6Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net