AK-LM 330 RS8FR302 © Danfoss 2015-08 75Alarm textsSettings DefaultpriorityAlarm text DescriptionSaux X sensor error(X=1-10)High Saux X sensor error Saux X temp. sensor signal is faultyPauxX sensor error(X=1-5)High Paux X sensor error Paux X pressure transmitter signal is faultyStandby mode Medium Control stopped,MainSwitch=OFFThe control has been stopped via the setting ”Main switch” = ON orvia the external Main switch inputThermostat X – Lowtemp. alarm(X=1-10)Medium Thermostat X - Low alarm Thermostat temperature has been below the set low temperaturelimit for longer time than set delayThermostat X – Hightemp. alarm(X=1-10)High Thermostat X - High alarm Thermostat temperature has been above the set high temperaturelimit for longer time than the set delayPressostat X – Low pres-sure alarm(X=1-5)Medium Pressostat X - Low alarm The pressure has been below the set low pressure limit for longerthan the set delayPressostat X – alarm limithigh pressure(X=1-5)Medium Pressostat X - High alarm The pressure has been above the high pressure limit for longer thanthe set delay timeVoltage input X – Lowalarm(X=1-5)Medium Analog input X - Low alarm The voltage signal has been below the low alarm limit for longertime than set delayVoltage input X – Highalarm(X=1-5)Medium Analog input X - High alarm The voltage signal has been above the high alarm limit for longertime than set delayDI X alarm input(X=1-16)Medium DI X alarm Alarm on general alarm input DI xSystem alarmsThe alarm priority can not be altered on system alarmsMedium Clock has not been set Time has not been setMedium System Critical exception A unrecoverable critical system failure has occurred – exchange thecontrollerMedium System alarm exception A minor system failure has occurred – power off controllerMedium Alarm destination disabled When this alarm is activated the alarm transmission to the alarmreceiver has been deactivated.When the alarm is cleared the alarm transmission to the alarmreceiver has been activated.Medium Alarm route failure Alarms can not be transmitted to alarm receiver – check communi-cationHigh Alarm router full The internal alarm buffer has an overrun – this might occur if thecontroller can not send the alarms to the alarm receiver. Check com-munication between controller and AKA gateway.Medium Device is restarting The controller is restarting after flash updating of the softwareMedium IO module error There is a communication fault between the controller module andthe extension modules – the fault must be corrected as soon aspossibleLow MAN DI………. The output in question has been put in manual control mode via theAK-ST 500 service tool softwareLow MAN DO……… The output in question has been put in manual control mode via theAK-ST 500 service tool software