Control & overviewsECL Card settings(circuit II)30bA Time and date Section 17B System information Sections 18 & 19C Heat curve Section 20Setting ranges Factory settings Your settingsSlope0.2 ... 3.4 0.6See section 20Parallel displacement-9 ... 9 K 0 KSee section 201Limit for heating cut-out10 ... 30 °C 20 °CSee section 212Flow temperature, min. / max. limits10 ... 150 °C min. 10, max. 50 °CSee section 223Room temperature influence0 ... 99 / -99 ... 0 min. 0, max. -40See section 234Proportional band, Xp1 ... 250 K 80 KSee section 265Integration time constant, Tn5 ... 999 sec. 30 sec.See section 266Running time of the motorized controlvalve5 ... 250 sec. 35 sec.See section 267Neutral zone, Nz0 ... 9 K 3 KSee section 26