DMS Manual Power WiringConnect the Supply voltage to the DMS inputterminals 1/L1, 3/L2 & 5/L3.The terminals in theExtended versions of the DMS allow two cablesto loop the power line as shown.. /0)( '/ ''/ /1+(' 01- 2( '(1+('' '(Looping the power line - 3-phase mainsConnect the Motor terminals to the DMS outputterminals 2/T1, 4/T2 & 6/T3. Take care of the phasesequence to have the correct direction of rotation.The terminals in the Extended versions of theDMS allow two cables to connect two motorsin parallel to one DMS.Maximum cross section: 4 mm sq. (10 AWG)For ST & SB versions, provide strain relief for powerand control cables by using the cable supportprovided in the DMS unit, as shown. Power factor correctionIf a DMS is used with static power factorcorrection it must be connected to thesupply side of the DMS.Connecting power factor correctioncapacitors to the output of the DMS will resultin damage to the DMS. Control WiringComplete the Control wiring as shown in theElectrical Schematic diagram.. /0)( '/ ''/ // ' ('34 '/5Connect Control Supply / AS-i Interface atthe terminals provided.Contacts used for controlling these inputs should below voltage, low current rated (Gold flash or similar)Maximum cross section: 2.5 mm2 (12 AWG)Use cables complying with local regulations.MG.05.A2.02 - VLT is a registered Danfoss trademark6