5.3 Flow temperatureThe ECL Comfort 210 / 296 / 310 controls the DHW temperatureaccording to the desired flow temperature for example under theinfluence of the return temperature.The desired DHW temperature is set in the overview display.50.3: Actual DHW temperature50: Desired DHW temperatureActual DHW temp.Desired DHWtemp.Parameters indicated with an ID no. like "1x607" mean a universalparameter.x stands for circuit / parameter group.MENU > Settings > Flow temperatureTemp. min. 1x177See Appendix “Parameter ID overview”Set the min. flow temperature for the system. The desired flowtemperature will not be lower than this setting. Adjust the factorysetting, if required.‘Temp. min.’ is overruled if 'Total stop' is active in Saving mode or'Cut-out' is active.‘Temp. min.’ can be overruled by the influence from the returntemperature limitation (see 'Priority').The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.MENU > Settings > Flow temperatureTemp. max. 1x178See Appendix “Parameter ID overview”Set the max. flow temperature for the system. The desiredtemperature will not be higher than this setting. Adjust the factorysetting, if required.The setting of ‘heat curve’ is possible for heating circuits only.The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.54 | © Danfoss | 2018.03 VI.LG.U3.02Operating Guide ECL Comfort 210/296/310, application A217/A317