7.5 DefinitionsThe definitions apply to the ECL Comfort 210 / 296 / 310 series.Consequently, you might come across expressions that are notmentioned in your guide.Accumulated temperature valueA filtered (dampened) value, typically for room and outdoortemperatures. Is calculated in the ECL controller and is usedto express the heat stored in the walls of the house. Theaccumulated value does not change so rapidly as the actualtemperature.Air duct temperatureTemperature measured in the air duct where the temperatureis to be controlled.Alarm functionBased on the alarm settings, the controller can activate an output.Anti-bacteria functionFor a defined period, the DHW temperature is increased in orderto neutralize dangerous bacteria, e.g. Legionella.Balance temperatureThis setpoint is the basis for the flow / air duct temperature. Thebalance temperature can be adjusted by the room temperature,the compensation temperature and the return temperature. Thebalance temperature is only active if a room temperature sensoris connected.BMSBuilding Management System. A supervisory system for remotecontrol and monitoring.Comfort operationNormal temperature in the system controlled by the schedule.During heating the flow temperature in the system is higher tomaintain the desired room temperature. During cooling the flowtemperature in the system is lower to maintain the desired roomtemperature.Comfort temperatureTemperature maintained in the circuits during comfort periods.Normally during daytime.Compensation temperatureA measured temperature influencing the flow temperaturereference / balance temperature.Desired flow temperatureTemperature calculated by the controller on basis of the outdoortemperature and influences from the room and / or returntemperatures. This temperature is used as a reference for thecontrol.Desired room temperatureTemperature which is set as the desired room temperature. Thetemperature can only be controlled by the ECL Comfort controllerif a room temperature sensor is installed.If a sensor is not installed, the set desired room temperaturehowever still influences the flow temperature.In both cases the room temperature in each room is typicallycontrolled by radiator thermostats / valves.Desired temperatureTemperature based on a setting or a controller calculation.Dew point temperatureTemperature at which the humidity in the air condensates.150 | © Danfoss | 2017.05 VI.LG.H4.02Operating Guide ECL Comfort 210/296/310, application A230