Installation Guide ECL Comfort 310, application A3766.7 ApplicationECA addr. (choice of Remote Control Unit) 12010Circuit Setting range Factory setting2 OFF / A / B OFFDecidesthecommunicationwiththeRemoteControlUnit.OFF: No Remote Control Unit. Only room temperature sensor,if any.A: Remote Control Unit ECA 30 / 31 with address A.B: Remote Control Unit ECA 30 / 31 with address B.The Remote Control Unit has no influence on the DHW control.The Remote Control Unit must be set accordingly (A or B).Send desired T 12500Circuit Setting range Factory setting2 OFF / ON ONWhen the controller acts as a slave controller in a master / slave system,informationaboutthedesiredflowtemperaturecanbesenttothemastercontroller via the ECL 485 bus.OFF: Information about the desired flow temperature is notsent to the master controller.ON: Information about the desired flow temperature is sentto the master controller.Inthemastercontroller,'Demandoffset'mustbesettoavalueinorderto react on a desired flow temperature from a slave controller.P exercise (pump exercise) 12022Circuit Setting range Factory setting2 OFF / ON ONExercisesthepumptoavoidblockinginperiodswithoutheatdemand.OFF: The pump exercise is not active.ON: The pump is switched ON for 1 minute every third day atnoon (12:14 hours).M exercise (valve exercise) 12023Circuit Setting range Factory setting2 OFF / ON OFFExercisesthevalvetoavoidblockinginperiodswithoutheatdemand.OFF: The valve exercise is not active.ON: The valve opens for 7 minutes and closes for 7 minutesevery third day at noon (12:00 hours).Danfoss District Energy VI.GU.B1.02 DEN-SMT/DK 119