Installation Guide ECL Comfort 310, application A3676.8 AlarmMany applications in the ECL Comfort 210 and 310 series have analarm function. The alarm function typically activates relay 4 (ECLComfort 210) or relay 6 (ECL Comfort 310).The alarm relay can activate a lamp, a horn, an input to an alarmtransmitting device etc. etc.The relay in question is activated as long as the alarm conditionis present.Typical alarms:• Actual flow temperature differs from the desired flowtemperature.• An activated circulation pump does not generate a pressuredifference.• The refill water function does not generate a pressure withina preset time.• A universal alarm input (application dependent) is activated.Upper difference 12147Circuit Setting range Factory setting2 OFF / 1 ... 30 K OFFThealarmisactivatediftheactualflowtemperatureincreasesmorethanthe set difference (acceptable temperature difference above the desiredflow temperature). See also 'Delay'.OFF: The alarm function is not active.1 ... 30 K: The alarm function is active if the actual temperaturegets above the acceptable difference.Flow temp. °CUpperdifference(setvalue)Desiredflowtemp.Outdoortemp.°CLower difference 12148Circuit Setting range Factory setting2 OFF / 1 ... 30 K OFFThealarmisactivatediftheactualflowtemperaturedecreasesmorethanthe set difference (acceptable temperature difference below the desiredflow temperature). See also 'Delay'.OFF: The alarm function is not active.1 ... 30 K: The alarm function is active if the actual temperaturegets below the acceptable difference.Flow temp. °CLowerdifference(setvalue)Desiredflowtemp.Outdoortemp.°CDanfoss District Energy VI.LG.R1.02 DEN-SMT/DK 105