5.9 Tank temperatureMENU > Settings > Tank temperatureDHW P post-run 1x041SettheDHWheatingpumppost-runtime(minutes). Thepumpcancontinueto be switched ON after the DHW heating procedure in order to utilize aremainingheat in the heat supplysystem.See Appendix “Parameter ID overview”0 ... 30: Set the number of minutes for the post-run.MENU > Settings > Tank temperatureChar. P post-run 1x042Set the DHW charging pump post-run time (minutes). The pump cancontinuetobeswitchedONaftertheDHWheatingprocedureinordertoutilizearemainingheatintheheat-exchanger.See Appendix “Parameter ID overview”0 ... 30: Set the number of minutes for the post-run.MENU > Settings > Tank temperatureCont. T control 1x054Depending on the DHW circulation pipe connection, the desired DHWheating / charging temperature can be lowered when the DHW heatingprocedure has elapsed.See Appendix “Parameter ID overview”OFF: The desired DHW heating temperature is lowered to 10°C. Typically, the DHW is circulated through the DHWtank.ON: The desired DHW heating temperature is lowered tothe desired DHW temperature. Typically, the DHWis circulated through the heat exchanger in order tocompensate for the heat loss in the DHW circulationpipe.MENU > Settings > Tank temperatureCirc. P priority 1x055Choose whether the DHW circulation pump should be ON during DHWheating.See Appendix “Parameter ID overview”OFF: The DHW circulation pump is switched OFF during DHWheating.ON: The DHW circulation pump is not switched OFF duringDHW heating.When the 'Circ. P priority' is set to OFF, the schedule for the DHWcirculation pump is overruled.VI.GU.O3.02 © Danfoss | 2017.08 | 101Operating Guide ECL Comfort 310, application P330