5.11 AlarmMany applications in the ECL Comfort 210 and 310 series have analarm function. The alarm function typically activates relay 4 (ECLComfort 210) or relay 6 (ECL Comfort 310).The alarm relay can activate a lamp, a horn, an input to an alarmtransmitting device etc.The relay in question is activated as long as the alarm conditionis present.Typical alarms:• Actual flow temperature differs from the desired flowtemperature.5.11.1 Temp. monitor.MENU > Settings > AlarmUpper difference 1x147Thealarmisactivatediftheactualflowtemperatureincreasesmorethanthe set difference (acceptable temperature difference above the desiredflow temperature). See also 'Delay'.See Appendix “Parameter ID overview”OFF: The alarm function is not active.1 ... 30 K: The alarm function is active if the actual temperaturegets above the acceptable difference.Flow temp. °CUpperdifference(setvalue)Desiredflowtemp.TimeMENU > Settings > AlarmLower difference 1x148Thealarmisactivatediftheactualflowtemperaturedecreasesmorethanthe set difference (acceptable temperature difference below the desiredflow temperature). See also 'Delay'.See Appendix “Parameter ID overview”OFF: The alarm function is not active.1 ... 30 K: The alarm function is active if the actual temperaturegets below the acceptable difference.Flow temp. °CLowerdifference(setvalue)Desiredflowtemp.TimeMENU > Settings > AlarmDelay 1x149Ifanalarmconditionfromeither'Upperdifference'or'Lowerdifference'ispresent for a longer time than the set delay (in min.), the alarm functionis activated.See Appendix “Parameter ID overview”1 ... 99 m: The alarm function will be activated if the alarmcondition remains after the set delay.Temp.Flow temp.Alarm limitTimeDelayVI.GU.O3.02 © Danfoss | 2017.08 | 109Operating Guide ECL Comfort 310, application P330