FC 300 Instruction ManualHow to Program" Basic Parameters0-01 LanguageOption:*English (ENGLISH) [0]German (DEUTSCH) [1]French (FRANCAIS) [2]Danish (DANSK) [3]Spanish (ESPANOL) [4]Italian (ITALIANO) [5]Chinese (CHINESE) [10]Function:Choose the desired LCP language.1-20 Motor Power [HP]Range:0.50 - 10 HP (0.37-7.5 kW) [Motortype de-pendent]Function:The value should equal the nameplate data on theconnected motor. The default value correspondsto the nominal rated output of the unit.NOTEChanging the value in this parameteraffects the setting of other parameters.Par. 1-20 cannot be changed whilethe motor is running.1-22 Motor VoltageRange:200-500 V [Motortype de-pendent]Function:The value should equal the nameplate data on theconnected motor. The default value correspondsto the nominal rated output of the unit.NOTEChanging the value in this parameteraffects the setting of other parameters.Par. 1-22 cannot be changed whilethe motor is running.1-23 Motor frequencyOption:*50 Hz (50 HZ) [50]60 Hz (60 HZ) [60]Min - Max motor frequency: 20 - 300 HzFunction:Select the stated value from the motor name plate.Alternatively, set the value for motor frequency tobe infinitely variable. If a value different from 50 Hzor 60 Hz is selected, it is necessary to correct par.1-50 to 1-54. For 87 Hz operation with 230/400 Vmotors, set the name plate data for 230 V/50 Hz.Adapt par. 2-02 Output speed high limit and par.2-05 Maximum reference to the 87 Hz application.NOTEChanging the value in this parameteraffects the setting of other parameters.Par. 1-23 cannot be changed whilethe motor is running.NOTEIf a delta connection is used, selectthe rated motor frequency for thedelta connection.1-24 Motor currentRange:Motor type dependent.Function:The value should equal the nameplate data onthe connected motor. Data is used for calculatingtorque, motor protection, etc.NOTEChanging the value in this parameteraffects the setting of other parameters.Par. 1-24 cannot be changed whilethe motor is running.1-25 Motor nominal speedRange:100 - 60000 RPM * RPMFunction:The value should equal the name plate dataon the connected motor. The data is used forcalculating motor compensations.* default setting ( ) display text [ ] value for use in communication via serial communication port32 MG.33.A2.22 - VLT is a registered Danfoss trademark