4. Press the navigation keys to scroll to0-03 Regional Settings and press [OK].0-0*Basic Settings0.0%0-03 Regional Settings[0] International0.00A 1(1)130BP088.10Illustration 3.3 0-03 Regional Settings5. Press the navigation keys to select Internationalor North America as appropriate and press [OK].(This changes the default settings for a numberof basic parameters. See for a complete list.)6. Press [Quick Menu] on the LCP.7. Press the navigation keys to scroll to parametergroup Q2 Quick Setup and press [OK].130BB847.10Q1 My Personal MenuQ2 Quick SetupQ5 Changes MadeQ6 Loggings13.7% 13.0A 1(1)Quick MenusIllustration 3.4 Q2 Quick Setup8. Select language and press [OK].130BT772.10Q20.0 Hz 0.00kW 1(1)Motor Setup1 - 21 Motor Power [kW]4.0 kWIllustration 3.5 Select Language9. A jumper wire should be in place betweencontrol terminals 12 and 27. If this is the case,leave 5-12 Terminal 27 Digital Input at factorydefault. Otherwise select No Operation. Forfrequency converters with an optional bypass, nojumper wire is required.10. 3-02 Minimum Reference11. 3-03 Maximum Reference12. 3-41 Ramp 1 Ramp Up Time13. 3-42 Ramp 1 Ramp Down Time14. 3-13 Reference Site. Linked to Hand/Auto* LocalRemote.3.4 Asynchronous Motor SetupEnter the motor data in parameters 1-20/1-21 to 1-25. Theinformation can be found on the motor nameplate.1. 1-20 Motor Power [kW] or 1-21 MotorPower [HP]1-22 Motor Voltage1-23 Motor Frequency1-24 Motor Current1-25 Motor Nominal Speed130BT772.10Q20.0 Hz 0.00kW 1(1)Motor Setup1 - 21 Motor Power [kW]4.0 kWIllustration 3.6 Motor Setup3.5 PM Motor Setup in VVCplusCAUTIONDo only use PM motor with fans and pumps.Initial Programming Steps1. Activate PM motor operation 1-10 MotorConstruction, select [1) PM, non salient SPM2. Make sure to set 0-02 Motor Speed Unit to [0] RPMProgramming motor data.After selecting PM motor in 1-10 Motor Construction, thePM motor-related parameters in parameter groups 1-2*,1-3* and 1-4* are active.The information can be found on the motor nameplateand in the motor data sheet.Following parameters must be programmed in the listedorder1. 1-24 Motor Current2. 1-26 Motor Cont. Rated Torque3. 1-25 Motor Nominal Speed4. 1-39 Motor Poles5. 1-30 Stator Resistance (Rs)Enter line to common stator winding resistance(Rs). If only line-line data are available, divide theline-line value with 2 to achieve the line tocommon (starpoint) value.Start Up and Functional Tes... VLT®AutomationDrive OperatingInstructionsMG33AM02 - VLT® is a registered Danfoss trademark 273 3