MCD 200 Design GuideMG.17.C3.02 – VLT is a registered Danfoss trademark 13MCD 201■ Control Circuits2 Wire Control()#(*+, -- --*) -#-- ()#(*+,. ' $ * Also resets the MCD 2013 Wire Control --()(*+ ,()(*+ ,. --*) -#-- '* Also resets the MCD 201■ FunctionalityUser Adjustments' / / // /012-"34(" "04%500000 000 00(!"("604%500000 000 0)6789" :248)6868/81 Initial TorqueValue:30% - 75% Initial Torque ✭ 75%Function:Determines the start torque generated by the motorwhen the start command is first applied.Description of choice:Set so that the motor begins to rotate as soon as thestart command is given.2 Ramp UpValue:2 - 20 seconds, Full Voltage ✭ 10 secondsFunction:Determines the time taken for voltage to be ramped upto line voltage.Description of choice:Set to optimise motor acceleration and/or startcurrent. Short ramp times result in quicker accelerationand higher start currents. Long ramp times result inslower acceleration and lower start current.3 Ramp DownValue:2 - 20 seconds, No Soft Stop ✭ No Soft StopFunction:Sets the time of the soft stop voltage ramp. The softstop function extends motor deceleration time byramping down voltage supplied to the motor when astop is initiated.