Technical data, mains supply 1 x 220 - 240 V/3 x 200-240VAccording to . internationalstandardsType 2803 2805 2807 2811 2815 2822 2822PD22840 2840PD2Output current IINV. [A] 2.2 3.2 4.2 6.0 6.8 9.6 9.6 16 16(3 x 200-240V) I MAX (60s) [A] 3.5 5.1 6.7 9.6 10.8 15.3 10.6 25.6 17.6Output power (230V)S INV. [KVA] 0.9 1.3 1.7 2.4 2.7 3.8 3.8 6.4 6.4Typical shaft output P M,N [kW] 0.37 0.55 0.75 1.1 1.5 2.2 2.2 3.7 3.7Typical shaft output P M,N [HP] 0.5 0.75 1.0 1.5 2.0 3.0 3.0 5.0 5.0Max. cable crosssection, motor[mm2 /AWG] 1) 4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10 16/6Input current I L,N [A] 5.9 8.3 10.6 14.5 15.2 - 22.0 - 31.0(1 x 220-240 V) I L,MAX (60s) [A] 9.4 13.3 16.7 23.2 24.3 - 24.3 - 34.5Input current I L,N [A] 2.9 4.0 5.1 7.0 7.6 8.8 8.8 14.7 14.7(3 x 200-240 V) I L,MAX (60s) [A] 4.6 6.4 8.2 11.2 12.2 14.1 9.7 23.5 16.2Max. cable crosssection, power[mm2 /AWG] 1) 4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10 16/6Max. pre-fuses IEC/UL 2) [A] 20/20 20/20 20/20 20/20 20/20 20/20 35/35 25/25 50/50Efficiency3) [%] 95 95 95 95 95 95 95 95 95Power loss at 100%load[W] 24 35 48 69 94 125 125 231 231Weight [kg] 2.0 2.0 2.0 2.0 2.0 3,7 6.0 6.0 18.50Enclosure4 type IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20/NEMA11. American Wire Gauge. Max. cable cross section isthe largest cable cross section that can be attached tothe terminals. Always observe national and local reg-ulations.2. Type gG pre-fuses must be used for installation ac-cording to IEC rules. If you want to maintain UL/cULyou must use pre-fuses of the type Bussmann KTN-R200 V, KTS-R 500 V or Ferraz Shawmut, type ATMR(max. 30A). The fuses must be placed for protection ina circuit that is capable of supplying a maximum of100,000 amps RMS (symmetrical), 500 V maximum.3. Measured using a 25 m screened/armoured motorcable with a rated load and rated frequency.4. IP20 is standard for VLT 2805-2875, whereasNEMA 1 is an option.MG.27.E2.02 - VLT is a registered Danfoss trademark 153All about VLT 2800