Operation & Display001 Language(language)Value:English (english) [0]German (deutsch) [1]French (francais) [2]Danish (dansk) [3]Spanish (espanol) [4]Italian (italiano) [5]Function:This parameter is used to choose the language to beshown in the display whenever the LCP control unit isconnected.Description of choice:There is a choice of the languages shown. The factorysetting may vary.002 Local/remote operation(OPERATION SITE)Value:Remote operation (REMOTE) [0]Local operation (LOCAL) [1]Function:There is a choice of two different modes of operationof the frequency converter; Remote operation [0] orLocal operation [1]. See also parameter 013 Local con-trol if Local operation [1] is selected.Description of choice:If Remote operation [0] is selected, the frequency con-verter is controlled via:1. the control terminals or via serial communi-cation.2. the [START] key. This cannot, however,override stop commands transmitted via thedigital inputs or via serial communication.3. the [STOP/RESET] and [JOG] keys, on thecondition that these are active.If Local operation [1], is selected, the frequency con-verter is controlled via:1. the [START] key. This cannot, however,override stop commands via the digital inputs(see parameter 013 Local control).2. the [STOP/RESET] and [JOG] keys, on thecondition that these are active.3. the [FWD/REV] key, on the condition that ishas been selected as active in parameter 016Local reversing, and that parameter 013 Localcontrol is set at Local control and open loop[1] or Local control as parameter 100 [3]. Pa-rameter 200 Output frequency range is set atBoth directions.4. parameter 003 Local reference where the ref-erence can be set using the [+] and [-] keys.5. an external control command that can beconnected to the digital inputs (see parame-ter 013 Local control).NB!The [JOG] and [FWD/REV] keys are lo-cated on the LCP control unit.003 Local reference(LOCAL REFERENCE)Value:Par. 013 Local control must be set to [1]or [2]:0 - fMAX (par. 202) 50 HzPar. 013 Local control must be set to [3] or[4].Ref MIN - Ref MAX (par. 204-205) 0,0Function:In this parameter, the local reference can be set man-ually. The unit of the local reference depends on theconfiguration selected in parameter 100 Configuration.Description of choice:In order to protect the local reference, parameter002 Local/remote operation must be set to Local op-eration [1]. Local reference cannot be set via serialcommunication.Setup configurationThere is a choice of four Setups (parameter Setups),which can be programmed independently of one an-other. The active Setup can be selected in parameter004 Active Setup. When an LCP 2 control unit is con-nected, the active Setup number will be appear in the= factory setting, () = display text, [] = value for use in communication via serial communication portMG.27.E2.02 - VLT is a registered Danfoss trademark 59Programming