Normal overload 110% for 1 minuteIP 20 / NEMA Chassis A2 A2 A2 A2 A2 A2 A2 A3 A3IP 21 / NEMA 1 A2 A2 A2 A2 A2 A2 A2 A3 A3IP 55 / NEMA 12 A5 A5 A5 A5 A5 A5 A5 A5 A5IP 66 / NEMA 12 A5 A5 A5 A5 A5 A5 A5 A5 A5Mains supply 200 - 240 VACFrequency converterTypical Shaft Output [kW] PK25 PK37 PK55 PK75P1K11.1P1K51.5P2K22.2P3K03P3K73.7Typical Shaft Output [HP] at 208 V 0.25 0.37 0.55 0.75 1.5 2.0 2.9 4.0 4.9Output currentContinuous(3 x 200-240 V ) [A] 1.8 2.4 3.5 4.6 6.6 7.5 10.6 12.5 16.7Intermittent(3 x 200-240 V ) [A] 1.98 2.64 3.85 5.06 7.26 8.3 11.7 13.8 18.4ContinuouskVA (208 V AC) [kVA] 0.65 0.86 1.26 1.66 2.38 2.70 3.82 4.50 6.00Max. cable size:(mains, motor, brake)[mm 2 /AWG] 2) 0.2 - 4 mm2 / 4 - 10 AWGMax. input currentContinuous(3 x 200-240 V ) [A] 1.6 2.2 3.2 4.1 5.9 6.8 9.5 11.3 15.0Intermittent(3 x 200-240 V ) [A] 1.7 2.42 3.52 4.51 6.5 7.5 10.5 12.4 16.5Max. pre-fuses1) [A] 10 10 10 10 20 20 20 32 32EnvironmentEstimated power lossat rated max. load [W] 4) 21 29 42 54 63 82 116 155 185Weight enclosure IP20 [kg] 4.9 4.9 4.9 4.9 4.9 4.9 4.9 6.6 6.6Weight enclosure IP21 [kg] 5.5 5.5 5.5 5.5 5.5 5.5 5.5 7.5 7.5Weight enclosure IP55 [kg] 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5Weight enclosure IP 66 [kg] 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5Efficiency 3) 0.94 0.94 0.95 0.95 0.96 0.96 0.96 0.96 0.963.1.1. Mains Supply 3 x 200 - 240 VAC3. VLT AQUA Selection VLT® AQUA Drive Design Guide40 MG.20.N3.02 - VLT® is a registered Danfoss trademark3