7 Specifications7.1 Electrical Data, 380–480 VVLT® AQUA Drive FC 202 N110K N132 N160High/normal load HO NO HO NO HO NO(High overload=150% current during 60 s, normaloverload=110% current during 60 s)Typical shaft output at 400 V [kW] 90 110 110 132 132 160Typical shaft output at 460 V [hp] 125 150 150 200 200 250Typical shaft output at 480 V [kW] 110 132 132 160 160 200Enclosure size D1h/D3h/D5h/D6hOutput current (3-phase)Continuous (at 400 V) [A] 177 212 212 260 260 315Intermittent (60 s overload) (at 400 V)[A] 266 233 318 286 390 347Continuous (at 460/480 V) [A] 160 190 190 240 240 302Intermittent (60 s overload) (at 460/480 V) [kVA] 240 209 285 264 360 332Continuous kVA (at 400 V) [kVA] 123 147 147 180 180 218Continuous kVA (at 460 V) [kVA] 127 151 151 191 191 241Continuous kVA (at 480 V) [kVA] 139 165 165 208 208 262Maximum input currentContinuous (at 400 V) [A] 171 204 204 251 251 304Continuous (at 460/480 V) [A] 154 183 183 231 231 291Maximum number and size of cables per phase- Mains, motor, brake, and load share [mm2 (AWG)] 2x95 (2x3/0) 2x95 (2x3/0) 2x95 (2x3/0)Maximum external mains fuses [A]1) 315 350 400Estimated power loss at 400 V [W]2), 3) 2031 2559 2289 2954 2923 3770Estimated power loss at 460 V [W]2), 3) 1828 2261 2051 2724 2089 3628Efficiency3) 0.98 0.98 0.98Output frequency [Hz] 0–590 0–590 0–590Heat sink overtemperature trip [°C (°F)] 110 (230) 110 (230) 110 (230)Control card overtemperature trip [°C (°F)] 75 (167) 75 (167) 75 (167)Table 7.1 Electrical Data for Enclosures D1h/D3h/D5h/D6h, Mains Supply 3x380–480 V AC1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.2) Typical power loss is at normal conditions and expected to be within±15% (tolerance relates to variety in voltage and cable conditions). Thesevalues are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies fordimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical controlcard power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options forslots A and B each add only 4 W.3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energyefficiency class, see chapter 7.5 Ambient Conditions. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.Specifications Design GuideMG22B222 Danfoss A/S © 01/2018 All rights reserved. 417 7