23-04 OccurrenceArray [10]Option: Function:Select which day(s) the Timed Action applies to. Specify working/non-working days in par.0-81 WorkingDays, par. 0-82 AdditionalWorking Days and par. 0-83 AdditionalNon-WorkingDays.[0] * All days[1] Working days[2] Non-working days[3] Monday[4] Tuesday[5] Wednesday[6] Thursday[7] Friday[8] Saturday[9] Sunday8.2.12. Water Application Functions, 29-**The group contains parameters used for monitoring water / wastewater applications.29-00 Pipe Fill EnableOption: Function:[0] * Disabled Select Enabled to fill pipes at a user specified rate.[1] Enabled Select Enabled to fill pipes with a user specified rate.29-01 Pipe Fill Speed [RPM]Range: Function:Speed LowLimit*[Speed Low Limit - Speed High Lim-it]Set the filling speed for filling horizontal pipe systems. The speed can be selected in Hz or RPMdepending on the choices made in par. 4-11 / par. 4-13 (RPM) or in par. 4-12 / par. 4-14 (Hz).29-02 Pipe Fill Speed [Hz]Range: Function:MotorSpeed LowLimit*[Speed Low Limit - Speed High Lim-it]Set the filling speed for filling horizontal pipe systems. The speed can be selected in Hz or RPMdepending on the choices made in par. 4-11 / par. 4-13 (RPM) or in par. 4-12 / par. 4-14 (Hz).29-03 Pipe Fill TimeRange: Function:0 s* [0 - 3600 s] Set the specified time for pipe filling of horizontal pipe systems.29-04 Pipe Fill RateRange: Function:0.001 units/s*[0.001 – 999999.999 units/s] Specifies the filling rate in units/second using the PI controller. Filling rate units are feedback units/second. This function is used for filling-up vertical pipe systems but will be active when the filling-time has expired, no matter what , until the pipe fill-set-point set in par. 29-05 is reached.VLT® AQUA DriveOperating Instructions 8. How to programme the frequency converterMG.20.M5.02 - VLT® is a registered Danfoss trademark 1078