It is recommended to do the set-up in the order listed.Illustration 8.1: Quick menu view.Par. Designation [Units]0-01 Language1-20 Motor Power [kW]1-22 Motor Voltage [V]1-23 Motor Frequency [Hz]1-24 Motor Current [A]1-25 Motor Nominal Speed [RPM]3-41 Ramp 1 Ramp up Time [s]3-42 Ramp 1 Ramp down Time [s]4-11 Motor Speed Low Limit [RPM]4-13 Motor Speed Low High [RPM]1-29 Automatic Motor Adaption [AMA]Table 8.2: Quick Setup parametersIfNo Operation is selected in terminal 27 no connection to +24 V on terminal 27 is necessary to enable start.IfCoast Inverse (factory default value) is selected in Terminal 27, a connection to +24V is necessary to enable start.8.1.3. Q1 My Personal MenuParameters defined by the user can be stored in Q1 My Personal Menu.SelectMy Personal Menu to display only the parameters, which have been pre-selected and programmed as personal parameters. For example, a pumpor equipment OEM may have pre-programmed these to be in My Personal Menu during factory commissioning to make on site commissioning / fine tuningsimpler.. These parameters are selected in par. 0-25My Personal Menu. Up to 20 different parameters can be defined in this menu.Q1 My Personal Menu20-21 Setpoint 120-93 PID Proportional Gain20-94 PID Integral Time8.1.4. Q2 Quick SetupThe parameters in Q2 Quick Setup are the basic parameters which are always needed to set-up the frequency converter to operation.Q2 Quick SetupParameter number and name Unit0-01 Language1-20 Motor Power kW1-22 Motor Voltage V1-23 Motor Frequency Hz1-24 Motor Current A1-25 Motor Nominal Speed RPM3-41 Ramp 1 Ramp Up Time s3-42 Ramp 1 Ramp Down Time s4-11 Motor Speed Low Limit RPM4-13 Motor Speed High Limit RPM1-29 Automatic Motor Adaptation (AMA)8. How to programme the frequency converterVLT® AQUA DriveOperating Instructions62 MG.20.M4.02 - VLT® is a registered Danfoss trademark8