Normal overload 110% for 1 minuteFrequency converterTypical Shaft Output [kW]P110110P132132P160160P200200P250250P315315P355355P400400P450450Typical Shaft Output [HP] at 460V 150 200 250 300 350 450 500 550 600IP 00 D3 D3 D4 D4 D4 E2 E2 E2 E2IP 21 D1 D1 D2 D2 D2 E1 E1 E1 E1IP 54 D1 D1 D2 D2 D2 E1 E1 E1 E1Output currentContinuous (3 x 400 V) [A] 212 260 315 395 480 600 658 745 800Intermittent (3 x 400 V) [A] 233 286 347 435 528 660 724 820 880Continuous (3 x 460-500V) [A] 190 240 302 361 443 540 590 678 730Intermittent (3 x 460-500V) [A] 209 264 332 397 487 594 649 746 803Continuous kVA (400 V AC) [kVA] 147 180 218 274 333 416 456 516 554Continuous kVA (460 V AC) [kVA] 151 191 241 288 353 430 470 540 582Max. cable size:(mains, motor, brake) [mm 2/ AWG] 2) 2x702x2/02x1852x350 mcm4x2404x500 mcmMax. input currentContinuous (3 x 400 V) [A] 204 251 304 381 463 590 647 733 787Continuous (3 x 460/500V) [A] 183 231 291 348 427 531 580 667 718Max. pre-fuses1)[A] 300 350 400 500 600 700 900 900 900EnvironmentEstimated power lossat rated max. load [W] 4) 3234 3782 4213 5119 5893 7630 7701 8879 9428Weight enclosure IP00 [kg] 81.9 90.5 111.8 122.9 137.7 221.4 234.1 236.4 277.3Weight enclosure IP 21 [kg] 95.5 104.1 125.4 136.3 151.3 263.2 270.0 272.3 313.2Weight enclosure IP 54 [kg] 95.5 104.1 125.4 136.3 151.3 263.2 270.0 272.3 313.2Efficiency 3) 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.981) For type of fuse see sectionFuses2) American Wire Gauge3) Measured using 5 m screened motor cables at rated load and rated frequency4) The typical power loss is at normal load conditions and expected to be within +/- 15% (tolerance relates to variety in voltage and cable conditions).Values are based on a typical motor efficiency (eff2/eff3 border line). Lower efficiency motors will also add to the power loss in the frequency converter and vice versa.If the switching frequency is raised from nominal the power losses may rise significantly.LCP and typical control card power consumptions are included. Further options and customer load may add up to 30W to the losses. (Though typically only 4W extra for a fully loaded control card, or options for slot A or slotB, each).Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/- 5%).5.1.1. Mains Supply 3 x 380 - 480 VAC5. General Specifications VLT AQUA High Power Operation Instructions130 MG.20.P1.02 - VLT ® is a registered Danfoss trademark5