[1659] Adjusted Setpoint Displays the actual operating set-point after it is modified by flow compensation. See parameters22-8*.[1660] Digital Input Displays the status of the digital inputs. Signal low = 0; Signal high = 1.Regarding order, see par. 16-60. Bit 0 is at the extreme right.[1661] Terminal 53 Switch Setting Setting of input terminal 53. Current = 0; Voltage = 1.[1662] Analog Input 53 Actual value at input 53 either as a reference or protection value.[1663] Terminal 54 Switch Setting Setting of input terminal 54. Current = 0; Voltage = 1.[1664] Analog Input 54 Actual value at input 54 either as reference or protection value.[1665] Analog Output 42 [mA] Actual value at output 42 in mA. Use par. 6-50 to select the variable to be represented by output42.[1666] Digital Output [bin] Binary value of all digital outputs.[1667] Freq. Input #29 [Hz] Actual value of the frequency applied at terminal 29 as a pulse input.[1668] Freq. Input #33 [Hz] Actual value of the frequency applied at terminal 33 as a pulse input.[1669] Pulse Output #27 [Hz] Actual value of pulses applied to terminal 27 in digital output mode.[1670] Pulse Output #29 [Hz] Actual value of pulses applied to terminal 29 in digital output mode.[1671] Relay Output [bin] View the setting of all relays.[1672] Counter A View the present value of Counter A.[1673] Counter B View the present value of Counter B.[1675] Analog input X30/11 Actual value of the signal on input X30/11 (General Purpose I/O Card. Option)[1676] Analog input X30/12 Actual value of the signal on input X30/12 (General Purpose I/O Card. Optional)[1677] Analog output X30/8 [mA] Actual value at output X30/8 (General Purpose I/O Card. Optional) Use Par. 6-60 to select the var-iable to be shown.[1680] Fieldbus CTW 1 Control word (CTW) received from the Bus Master.[1682] Fieldbus REF 1 Main reference value sent with control word via the serial communications network e.g. from theBMS, PLC or other master controller.[1684] Comm. Option STW Extended fieldbus communication option status word.[1685] FC Port CTW 1 Control word (CTW) received from the Bus Master.[1686] FC Port REF 1 Status word (STW) sent to the Bus Master.[1690] Alarm Word One or more alarms in a Hex code (used for serial communications)[1691] Alarm Word 2 One or more alarms in a Hex code (used for serial communications)[1692] Warning Word One or more warnings in a Hex code (used for serial communications)[1693] Warning Word 2 One or more warnings in a Hex code (used for serial communications)[1694] Ext. Status Word One or more status conditions in a Hex code (used for serial communications)[1695] Ext. Status Word 2 One or more status conditions in a Hex code (used for serial communications)[1696] Maintenance Word The bits reflect the status for the programmed Preventive Maintenance Events in parameter group23-1*[1830] Analog Input X42/1 Shows the value of the signal applied to terminal X42/1 on the Analog I/O card.[1831] Analog Input X42/3 Shows the value of the signal applied to terminal X42/3 on the Analog I/O card.[1832] Analog Input X42/5 Shows the value of the signal applied to terminal X42/5 on the Analog I/O card.[1833] Analog Out X42/7 [V] Shows the value of the signal applied to terminal X42/7 on the Analog I/O card.[1834] Analog Out X42/9 [V] Shows the value of the signal applied to terminal X42/9 on the Analog I/O card.[1835] Analog Out X42/11 [V] Shows the value of the signal applied to terminal X42/11 on the Analog I/O card.[2117] Ext. 1 Reference [Unit] The value of the reference for extended Closed Loop Controller 1[2118] Ext. 1 Feedback [Unit] The value of the feedback signal for extended Closed Loop Controller 1[2119] Ext. 1 Output [%] The value of the output from extended Closed Loop Controller 1[2137] Ext. 2 Reference [Unit] The value of the reference for extended Closed Loop Controller 2[2138] Ext. 2 Feedback [Unit] The value of the feedback signal for extended Closed Loop Controller 2[2139] Ext. 2 Output [%] The value of the output from extended Closed Loop Controller 25 How to programme the frequency converter VLT AQUA High Power Operation Instructions102 MG.20.P3.02 - VLT® is a registered Danfoss trademark5