Mains Supply 3 x 525- 690 VACP710 P800 P900 P1M0 P1M2Typical Shaft output at550 V [kW] 560 670 750 850 1000Typical Shaft output at575 V [HP] 750 950 1050 1150 1350Typical Shaft output at690 V [kW] 710 800 900 1000 1200Enclosure IP21, 54without/ with optionscabinetF1/ F3 F1/ F3 F1/ F3 F2/ F4 F2/ F4Output currentContinuous(at 550 V) [A] 763 889 988 1108 1317Intermittent (60 s over-load, at 550 V) [A] 839 978 1087 1219 1449Continuous(at 575/ 690 V) [A] 730 850 945 1060 1260Intermittent (60 s over-load, at 575/690 V) [A] 803 935 1040 1166 1386Continuous KVA(at 550 V) [KVA] 727 847 941 1056 1255Continuous KVA(at 575 V) [KVA] 727 847 941 1056 1255Continuous KVA(at 690 V) [KVA] 872 1016 1129 1267 1506Max. input currentContinuous(at 550 V ) [A] 743 866 962 1079 1282Continuous(at 575 V) [A] 711 828 920 1032 1227Continuous(at 690 V) [A] 711 828 920 1032 1227Max. cable size,motor[mm2 (AWG 2))]8x150(8x300 mcm)12x150(12x300 mcm)Max. cable size,mains[mm2 (AWG 2))]8x240(8x500 mcm)Max. cable size, load-sharing [mm 2 (AWG 2))]4x120(4x250 mcm)Max. cable size, brake[mm2 (AWG 2))4x185(4x350 mcm)6x185(6x350 mcm)Max. external pre-fuses[A] 1) 1600 2000Est. power lossat rated max. load [W]4), 575 V, F1 & F210771 12272 13835 15592 18281Est. power lossat rated max. load [W]4), 690 V, F1 & F211315 12903 14533 16375 19207Max added losses ofCircuit Breaker or Dis-connect & Contactor,F3 & F4422 526 610 658 855Max Panel Options Los-ses 400Weight,enclosure IP21,IP 54 [kg] 1004/ 1299 1004/ 1299 1004/ 1299 1246/ 1541 1246/ 1541Weight, RectifierModule [kg] 102 102 102 136 136Weight, InverterModule [kg] 102 102 136 102 102Efficiency4) 0.98Output frequency 0-500 HzHeatsink overtemp. trip 85 °CPower card amb. trip 68 °C1) For type of fuse see sectionFuses.2) American Wire Gauge.3) Measured using 5 m screened motor cables at rated load and rated frequency.4) The typical power loss is at nominal load conditions and expected to be within +/-15% (tolerence relates to variety in voltage and cableconditions). Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power lossin the frequency converter and opposite. If the switching frequency is increased compared to the default setting, the power losses may risesignificantly.LCP and typical control card power consumptions are included. Further options and customer load may add up to 30W to the losses.(Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B, each).Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).6 General Specifications VLT AQUA High Power Operation Instructions182 MG.20.P3.02 - VLT® is a registered Danfoss trademark6