6.4.18 22-** Application FunctionsPar.No. #Parameter description Default value(SR = Size related)4 set-up Change dur-ing operationConver-sion indexType22-0* Miscellaneous22-00 External Interlock Delay 0 s All set-ups TRUE 0 Uint1622-01 Power Filter Time 0.50 s 2 set-ups TRUE -2 Uint1622-2* No-Flow Detection22-20 Low Power Auto Set-up [0] OFF All set-ups FALSE - Uint822-21 Low Power Detection [0] Disabled All set-ups TRUE - Uint822-22 Low Speed Detection [0] Disabled All set-ups TRUE - Uint822-23 No-Flow Function [0] OFF All set-ups TRUE - Uint822-24 No-Flow Delay 10 s All set-ups TRUE 0 Uint1622-26 Dry Pump Function [0] OFF All set-ups TRUE - Uint822-27 Dry Pump Delay 10 s All set-ups TRUE 0 Uint1622-3* No-Flow Power Tuning22-30 No-Flow Power 0.00 kW All set-ups TRUE 1 Uint3222-31 Power Correction Factor 100 % All set-ups TRUE 0 Uint1622-32 Low Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint1622-33 Low Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint1622-34 Low Speed Power [kW] ExpressionLimit All set-ups TRUE 1 Uint3222-35 Low Speed Power [HP] ExpressionLimit All set-ups TRUE -2 Uint3222-36 High Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint1622-37 High Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint1622-38 High Speed Power [kW] ExpressionLimit All set-ups TRUE 1 Uint3222-39 High Speed Power [HP] ExpressionLimit All set-ups TRUE -2 Uint3222-4* Sleep Mode22-40 Minimum Run Time 10 s All set-ups TRUE 0 Uint1622-41 Minimum Sleep Time 10 s All set-ups TRUE 0 Uint1622-42 Wake-up Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint1622-43 Wake-up Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint1622-44 Wake-up Ref./FB Difference 10 % All set-ups TRUE 0 Int822-45 Setpoint Boost 0 % All set-ups TRUE 0 Int822-46 Maximum Boost Time 60 s All set-ups TRUE 0 Uint1622-5* End of Curve22-50 End of Curve Function [0] OFF All set-ups TRUE - Uint822-51 End of Curve Delay 10 s All set-ups TRUE 0 Uint1622-6* Broken Belt Detection22-60 Broken Belt Function [0] OFF All set-ups TRUE - Uint822-61 Broken Belt Torque 10 % All set-ups TRUE 0 Uint822-62 Broken Belt Delay 10 s All set-ups TRUE 0 Uint1622-7* Short Cycle Protection22-75 Short Cycle Protection [0] Disabled All set-ups TRUE - Uint822-76 Interval between Startsstart_to_start_min_on_time(P2277) All set-ups TRUE 0 Uint1622-77 Minimum Run Time 0 s All set-ups TRUE 0 Uint1622-78 Minimum Run Time Override [0] Disabled All set-ups FALSE - Uint822-79 Minimum Run Time Override Value 0.000 ProcessCtrlUnit All set-ups TRUE -3 Int3222-8* Flow Compensation22-80 Flow Compensation [0] Disabled All set-ups TRUE - Uint822-81 Square-linear Curve Approximation 100 % All set-ups TRUE 0 Uint822-82 Work Point Calculation [0] Disabled All set-ups TRUE - Uint822-83 Speed at No-Flow [RPM] ExpressionLimit All set-ups TRUE 67 Uint1622-84 Speed at No-Flow [Hz] ExpressionLimit All set-ups TRUE -1 Uint1622-85 Speed at Design Point [RPM] ExpressionLimit All set-ups TRUE 67 Uint1622-86 Speed at Design Point [Hz] ExpressionLimit All set-ups TRUE -1 Uint1622-87 Pressure at No-Flow Speed 0.000 N/A All set-ups TRUE -3 Int3222-88 Pressure at Rated Speed 999999.999 N/A All set-ups TRUE -3 Int3222-89 Flow at Design Point 0.000 N/A All set-ups TRUE -3 Int3222-90 Flow at Rated Speed 0.000 N/A All set-ups TRUE -3 Int326 How to Program the Low Harmonic DriveVLT AQUA Low Harmonic Drive InstructionManual6-62 MG.20.T1.22 - VLT® is a registered Danfoss trademark6