FC 300 Design GuideHow to Program" Parameters: Digital In/Out" 5-0* Digital I/O Mode5-00 Digital I/O ModeOption:*PNP [0]NPN [1]Function:The digital inputs and programmed digitaloutputs are pre-programmable for operationeither in PNP or NPN systems.PNP systems are pulled down to GND. Actionis on positive going pulses (↑).NPN systems are pulled up to + 24 V (internal in thedrive). Action is on negative going pulse (↓).It is not possible to set the parameter whilethe motor is running.5-01 Terminal 27 ModeOption:*Input [0]Output [1]Function:Selects terminal 27 as either a digital input oroutput. Default setting is the Input function. Youcannot set this parameter while the motor is running.5-02 Terminal 29 ModeOption:*Input [0]Output [1]Function:Selects terminal 29 as either a digital input oroutput. Default setting is the Input function. Youcannot set the parameter while the motor is running." 5-1* Digital InputsParameters for configuring the input functionsfor the input terminals.The digital inputs are used for selecting variousfunctions in the adjustable frequency drive. Alldigital inputs can be set to the following functions:No operation [0]Reset [1]Coast inverse [2]Coast and reset inv. [3]Quick stop inverse [4]DC brake inverse [5]Stop inverse [6]Start [8]Latched start [9]Reverse [10]Start reverse [11]Enable start forward [12]Enable start reverse [13]Jog [14]Preset ref bit 0 [16]Preset ref bit 1 [17]Preset ref bit 2 [18]Freeze reference [19]Freeze output [20]Speed up [21]Slow [22]Set-up select bit 0 [23]Set-up select bit 1 [24]Catch up [28]Slow-down [29]Pulse input [32]Ramp bit 0 [34]Ramp bit 1 [35]Mains failure inverse [36]DigiPot increase [55]DigiPot decrease [56]DigiPot clear [57]Reset Counter A [62]Reset Counter B [65]Functions dedicated to only one digital input arestated in the belonging parameter.You can program all digital inputs to these functions:ï No operation [0]: The adjustablefrequency drive does not react on signalstransmitted to the terminal.ï Reset [1]: Resets the adjustablefrequency drive after a TRIP/ALARM. Notall alarms can be reset.ï Coast inverse [2] (Default Digital input27): Coasting stop, inverted input (NC). Theadjustable frequency drive leaves the motor infree mode. Logic í0í => coasting stop.ï Coast and reset inv. [3]: Reset andcoasting stop Inverted input (NC). Theadjustable frequency drive leaves the motorin free mode and resets the drive. Logicí0í => coasting stop and resetï Quick stop inverse [4]: Inverted input(NC). Generates a stop in accordance with* default setting ( ) display text [ ] value for use in communication via serial communication port166 MG.33.B3.22 - VLT is a registered Danfoss trademark