Recommended initialisation procedure, viaparameter 14-22 Operation Mode1. Press [Main Menu] twice to access parameters.2. Scroll to parameter 14-22 Operation Mode andpress [OK].3. Scroll to [2] Initialisation and press [OK].4. Remove power to the unit and wait for thedisplay to turn off.5. Apply power to the unit.Default parameter settings are restored during start-up.This may take slightly longer than normal.6. Alarm 80, Drive initialised to default value isshowed.7. Press [Reset] to return to operation mode.Manual initialisation procedure1. Remove power to the unit and wait for thedisplay to turn off.2. Press and hold [Status], [Main Menu], and [OK] atthe same time while applying power to the unit(approximately 5 s or until audible click and fanstarts).Factory default parameter settings are restored duringstart-up. This may take slightly longer than usual.Manual initialisation does not reset the following frequencyconverter information:• Parameter 15-00 Operating hours.• Parameter 15-03 Power Up's.• Parameter 15-04 Over Temp's.• Parameter 15-05 Over Volt's.5.4 Basic Programming5.4.1 Commissioning with SmartStartThe SmartStart wizard enables fast configuration of basicmotor and application parameters.• SmartStart starts automatically at first power-upor after initialisation of the frequency converter.• Follow the on-screen instructions to complete thecommissioning of the frequency converter.Always reactivate SmartStart by selecting QuickMenu Q4 - SmartStart.• For commissioning without use of the SmartStartwizard, refer to chapter 5.4.2 Commissioning via[Main Menu] or the programming guide.NOTICEMotor data is required for the SmartStart set-up. Therequired data is normally available on the motornameplate.5.4.2 Commissioning via [Main Menu]Recommended parameter settings are intended for start-up and check-out purposes. Application settings may vary.Enter data with power ON, but before operating thefrequency converter.1. Press [Main Menu] on the LCP.2. Press the navigation keys to scroll to parametergroup 0-** Operation/Display and press [OK].130BP066.101107 RPM0 - ** Operation/Display1 - ** Load/Motor2 - ** Brakes3 - ** Reference / Ramps3.84 A 1 (1)Main MenuIllustration 5.2 Main Menu3. Press the navigation keys to scroll to parametergroup 0-0* Basic Settings and press [OK].0-**Operation / Display0.0%0-0* Basic Settings0-1 * Set-up Operations0-2 * LCP Display0-3 * LCP Custom Readout0.00A 1(1)130BP087.10Illustration 5.3 Operation/Display4. Press the navigation keys to scroll toparameter 0-03 Regional Settings and press [OK].0-0*Basic Settings0.0%0-03 Regional Settings[0] International0.00A 1(1)130BP088.10Illustration 5.4 Basic Settings5. Press the navigation keys to select [0] Interna-tional or [1] North America as appropriate andCommissioning Operating InstructionsMG33AQ02 Danfoss A/S © 07/2015 All rights reserved. 255 5