7.2 Electrical Data, 525–690 VVLT® AutomationDrive FC 302 N55K N75K N90K N110 N132High/normal overload HO NO HO NO HO NO HO NO HO NO(High overload=150% current during60 s, normal overload=110% currentduring 60 s)Typical shaft output at 525 V [kW] 45 55 55 75 75 90 90 110 110 132Typical shaft output at 575 V [hp] 60 75 75 100 100 125 125 150 150 200Typical shaft output at 690 V [kW] 55 75 75 90 90 110 110 132 132 160Enclosure size D1h/D3h/D5h/D6hOutput current (3-phase)Continuous (at 525 V) [A] 76 90 90 113 113 137 137 162 162 201Intermittent (60 s overload)(at 525 V) [A]114 99 135 124 170 151 206 178 243 221Continuous (at 575/690 V) [A] 73 86 86 108 108 131 131 155 155 192Intermittent (60 s overload)(at 575/690 V) [A]110 95 129 119 162 144 197 171 233 211Continuous kVA (at 525 V) [kVA] 69 82 82 103 103 125 125 147 147 183Continuous kVA (at 575 V) [kVA] 73 86 86 108 108 131 131 154 154 191Continuous kVA (at 690 V) [kVA] 87 103 103 129 129 157 157 185 185 230Maximum input currentContinuous (at 525 V) [A] 74 87 87 109 109 132 132 156 156 193Continuous (at 575/690 V) 70 83 83 104 104 126 126 149 149 185Maximum number and size of cables per phase- Mains, motor, brake, and load share[mm2 (AWG)]2x95 (2x3/0) 2x95 (2x3/0) 2x95 (2x3/0) 2x95 (2x3/0) 2x95 (2x3/0)Maximum external mains fuses [A]1) 160 315 315 315 315Estimated power loss at 575 V [W]2), 3) 1098 1162 1162 1428 1430 1740 1742 2101 2080 2649Estimated power loss at 690 V [W]2), 3) 1057 1204 1205 1477 1480 1798 1800 2167 2159 2740Efficiency3) 0.98 0.98 0.98 0.98 0.98Output frequency [Hz] 0–590 0–590 0–590 0–590 0–590Heat sink overtemperature trip [°C (°F)] 110 (230) 110 (230) 110 (230) 110 (230) 110 (230)Control card overtemperature trip [°C(°F)]75 (167) 75 (167) 75 (167) 75 (167) 75 (167)Table 7.5 Electrical Data for Enclosures D1h/D3h/D5h/D6h, Mains Supply 3x525–690 V AC1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.2) Typical power loss is at normal conditions and expected to be within±15% (tolerance relates to variety in voltage and cable conditions). Thesevalues are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies fordimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical controlcard power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options forslots A and B each add only 4 W.3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energyefficiency class, see chapter 10.11 Efficiency. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.Specifications VLT® AutomationDrive FC 30240 Danfoss A/S © 01/2018 All rights reserved. MG38C20277