3.21 Parameters: 35-** Sensor Input Option3.21.1 35-0* Temp. Input Mode (MCB 114)35-00 Term. X48/4 Temperature UnitSelect the unit to be used with temperature input X48/4 settingsand readouts:Option: Function:[60] * °C[160] °F35-01 Term. X48/4 Input TypeView the temperature sensor type detected at input X48/4:Option: Function:[0] * Not Connected[1] PT100 2-wire[3] PT1000 2-wire[5] PT100 3-wire[7] PT1000 3-wire35-02 Term. X48/7 Temperature UnitSelect the unit to be used with temperature input X48/7 settingsand readouts:Option: Function:[60] * °C[160] °F35-03 Term. X48/7 Input TypeView the temperature sensor type detected at input X48/7:Option: Function:[0] * Not Connected[1] PT100 2-wire[3] PT1000 2-wire[5] PT100 3-wire[7] PT1000 3-wire35-04 Term. X48/10 Temperature UnitSelect the unit to be used with temperature input X48/10settings and readouts:Option: Function:[60] * °C[160] °F35-05 Term. X48/10 Input TypeView the temperature sensor type detected at input X48/10:Option: Function:[0] * Not Connected[1] PT100 2-wire[3] PT1000 2-wire[5] PT100 3-wire[7] PT1000 3-wire35-06 Temperature Sensor Alarm FunctionSelect the alarm function:Option: Function:[0] Off[2] Stop[5] * Stop and trip3.21.2 35-1* Temp. Input X48/4 (MCB 114)35-14 Term. X48/4 Filter Time ConstantRange: Function:0.001 s* [0.001 - 10s]Enter the filter time constant. This is afirst-order digital low pass filter timeconstant for suppressing electrical noisein terminal X48/4. A high time constantvalue improves dampening but alsoincreases the time delay through thefilter.35-15 Term. X48/4 Temp. MonitorThis parameter gives the possibility of enabling or disabling thetemperature monitor for terminal X48/4. The temperature limitscan be set in parameter 35-16 Term. X48/4 Low Temp. Limit andparameter 35-17 Term. X48/4 High Temp. Limit.Option: Function:[0] * Disabled[1] Enabled35-16 Term. X48/4 Low Temp. LimitRange: Function:Size related* [ -50 - par.35-17 ]Enter the minimum temperaturereading that is expected fornormal operation of thetemperature sensor at terminalX48/4.35-17 Term. X48/4 High Temp. LimitRange: Function:Size related* [ par. 35-16 -204 ]Enter the maximum temperaturereading that is expected fornormal operation of thetemperature sensor at terminalX48/4.3.21.3 35-2* Temp. Input X48/7 (MCB 114)35-24 Term. X48/7 Filter Time ConstantRange: Function:0.001 s* [0.001 - 10s]Enter the filter time constant. This is afirst-order digital lowpass filter timeconstant for suppressing electrical noisein terminal X48/7. A high time constantvalue improves dampening but alsoParameter Descriptions VLT® AutomationDrive FC 301/302 Programming GuideMG33MI02 - Rev. 2013-11-20 1713 3