7.2 Electrical Data7.2.1 Mains Supply 3x380–480 V AC Normal and High OverloadEnclosure MH1 MH2 MH3PK55 PK75 P1K1 P1K5 P2K2 P3K0 P4K0 P5K5Overload1) NO HO NO HO NO HO NO HO NO HO NO HO NO HOTypical shaftoutput [kW] 0.55 0.75 1.1 1.5 2.2 3.0 4.0Typical shaftoutput [hp] 0.75 1.0 1.5 2.0 3.0 4.0 5.0Maximum cablecross-section interminals2)(mains, motor)[mm2/AWG]4/12 4/12 4/12 4/12 4/12 4/12 4/12Output current40 °C ambient temperatureContinuous(3x380–440 V) [A] 1.7 2.2 3.0 3.7 5.3 7.2 9.0Intermittent(3x380–440 V) [A] 1.9 2.7 2.4 3.5 3.3 4.8 4.1 5.9 5.8 8.5 7.9 11.5 9.9 14.4Continuous(3x440–480 V) [A] 1.6 2.1 2.8 3.4 4.8 6.3 8.2Intermittent(3x440–480 V) [A] 1.8 2.6 2.3 3.4 3.1 4.5 3.7 5.4 5.3 7.7 6.9 10.1 9.0 13.2Maximum input currentContinuous(3x380–440 V) [A] 1.3 2.1 2.4 3.5 4.7 6.3 8.3Intermittent(3x380–440 V) [A] 1.4 2.0 2.3 2.6 2.6 3.7 3.9 4.6 5.2 7.0 6.9 9.6 9.1 12.0Continuous(3x440–480 V) [A] 1.2 1.8 2.2 2.9 3.9 5.3 6.8Intermittent(3x440–480 V) [A] 1.3 1.9 2.0 2.5 2.4 3.5 3.2 4.2 4.3 6.3 5.8 8.4 7.5 11.0Maximum mainsfuses See chapter 7.10 Fuse and Circuit Breaker Specifications.Estimated powerloss [W], bestcase/typical3)38 44 57 73 91 129 143Efficiency [%], bestcase/typical4)5) 0.96 0.97 0.97 0.97 0.97 0.97 0.97Table 7.10 Mains Supply 3x380–480 V AC Normal and High Overload: MH1, MH2, and MH3 Enclosure1) NO: Normal overload, 110% for 1 minute. HO: High overload, 160% for 1 minute.A frequency converter intended for HO requires a corresponding motor rating. For example, Table 7.10 shows that a 1.5 kW motor for HO requiresa P2K2 frequency converter.2) Maximum cable cross-section is the largest cable cross-section that can be attached to the terminals. Always observe national and localregulations.3) Applies to dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses mayincrease. LCP and typical control card power consumptions are included. For power loss data according to EN 50-598-2, refer towww.danfoss.com/vltenergyefficiency.4) Efficiency measured at nominal current. For energy efficiency class, see chapter 7.5 Ambient Conditions. For part load losses, seewww.danfoss.com/vltenergyefficiency.5) Measured using 4 m screened motor cables at rated load and rated frequency.Specifications VLT® DriveMotor FCP 106/FCM 10646 Danfoss A/S © 11/2015 All rights reserved. MG03L30277