4.1.4. Extended status wordsExtended status word, Par. 16-94Bit(Hex)Extended Status Word(Par. 16-94)00000001 Ramping00000002 AMA tuning00000004 Start CW/CCW00000008 Not used00000010 Not used00000020 Feedback high00000040 Feedback low00000080 Output current high00000100 Output current low00000200 Output frequency high00000400 Output frequency low00000800 Brake check OK00001000 Braking max00002000 Braking00004000 Out of speed range00008000 OVC active00010000 AC brake00020000 Password Timelock00040000 Password Protection00080000 Reference high00100000 Reference low00200000 Local Ref./Remote Ref.00400000 Reserved00800000 Reserved01000000 Reserved02000000 Reserved04000000 Reserved08000000 Reserved10000000 Reserved20000000 Reserved40000000 Reserved80000000 ReservedExtended status word 2, 16-95Bit(Hex) Extended Status Word 2 (Par. 16-95)00000001 Off00000002 Hand / Auto00000004 Not used00000008 Not used00000010 Not used00000020 Relay 123 active00000040 Start Prevented00000080 Control ready00000100 Drive ready00000200 Quick Stop00000400 DC Brake00000800 Stop00001000 Standby00002000 Freeze Output Request00004000 Freeze Output00008000 Jog Request00010000 Jog00020000 Start Request00040000 Start00080000 Start Applied00100000 Start Delay00200000 Sleep00400000 Sleep Boost00800000 Running01000000 Bypass02000000 Fire Mode04000000 Reserved08000000 Reserved10000000 Reserved20000000 Reserved40000000 Reserved80000000 Reserved4. Troubleshooting VLT® HVAC Drive Programming Guide236 MG.11.C5.02 - VLT® is a registered Danfoss trademark4