6.1.3 3x525–600 V ACFrequency converter P2K2 P3K0 P3K7 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90KTypical shaft output [kW] 2.2 3.0 3.7 5.5 7.5 11.0 15.0 18.5 22.0 30.0 37 45.0 55.0 75.0 90.0Typical shaft output [hp] 3.0 4.0 5.0 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0 70.0 100.0 125.0Protection rating IP20 H9 H9 H9 H9 H9 H10 H10 H6 H6 H6 H7 H7 H7 H8 H8Maximum cable size interminals (mains, motor)[mm2 (AWG)]4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 10 (8) 10 (8) 35 (2) 35(2)35(2)50(1)50(1)50(1)95(0)120(4/0)Output current - 40 °C (104 ° F) ambient temperatureContinuous (3x525–550 V) [A] 4.1 5.2 6.4 9.5 11.5 19.0 23.0 28.0 36.0 43.0 54.0 65.0 87.0 105.0 137.0Intermittent (3x525–550 V) [A] 4.5 5.7 7.0 10.5 12.7 20.9 25.3 30.8 39.6 47.3 59.4 71.5 95.7 115.5 150.7Continuous (3x551–600 V) [A] 3.9 4.9 6.1 9.0 11.0 18.0 22.0 27.0 34.0 41.0 52.0 62.0 83.0 100.0 131.0Intermittent (3x551–600 V) [A] 4.3 5.4 6.7 9.9 12.1 19.8 24.2 29.7 37.4 45.1 57.2 68.2 91.3 110.0 144.1Maximum input currentContinuous (3x525–550 V) [A] 3.7 5.1 5.0 8.7 11.9 16.5 22.5 27.0 33.1 45.1 54.7 66.5 81.3 109.0 130.9Intermittent (3x525–550 V) [A] 4.1 5.6 6.5 9.6 13.1 18.2 24.8 29.7 36.4 49.6 60.1 73.1 89.4 119.9 143.9Continuous (3x551–600 V) [A] 3.5 4.8 5.6 8.3 11.4 15.7 21.4 25.7 31.5 42.9 52.0 63.3 77.4 103.8 124.5Intermittent (3x551–600 V) [A] 3.9 5.3 6.2 9.2 12.5 17.3 23.6 28.3 34.6 47.2 57.2 69.6 85.1 114.2 137.0Maximum mains fuses SeeEstimated power loss [W],best case/typical1) 65 90 110 132 180 216 294 385 458 542 597 727 1092 1380 1658Weight enclosure protectionrating IP54 [kg (lb)] 6.6(14.6)6.6(14.6)6.6(14.6)6.6(14.6)6.6(14.6)11.5(25.3)11.5(25.3)24.5(54)24.5(54)24.5(54)36.0(79.3)36.0(79.3)36.0(79.3)51.0(112.4)51.0(112.4)Efficiency [%],best case/typical2) 97.9 97 97.9 98.1 98.1 98.4 98.4 98.4 98.4 98.5 98.5 98.7 98.5 98.5 98.5Output current - 50 °C (122 °F) ambient temperatureContinuous (3x525–550 V) [A] 2.9 3.6 4.5 6.7 8.1 13.3 16.1 19.6 25.2 30.1 37.8 45.5 60.9 73.5 95.9Intermittent (3x525–550 V) [A] 3.2 4.0 4.9 7.4 8.9 14.6 17.7 21.6 27.7 33.1 41.6 50.0 67.0 80.9 105.5Continuous (3x551–600 V) [A] 2.7 3.4 4.3 6.3 7.7 12.6 15.4 18.9 23.8 28.7 36.4 43.3 58.1 70.0 91.7Intermittent (3x551–600 V) [A] 3.0 3.7 4.7 6.9 8.5 13.9 16.9 20.8 26.2 31.6 40.0 47.7 63.9 77.0 100.9Table 6.6 3x525–600 V AC, 2.2–90 kW (3–125 hp), Enclosure Sizes H6–H101) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses mayincrease. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency.2) Efficiency measured at nominal current. For energy efficiency class, see chapter 6.3.12 Ambient Conditions. For part load losses, seewww.danfoss.com/vltenergyefficiency.Specifications VLT® HVAC Basic Drive FC 10148 Danfoss A/S © 05/2016 All rights reserved. MG18A80266