• Restoring factory default settings does notchange data stored in the LCP memory.5.3.4 Uploading/Downloading Data to/fromthe LCP1. Press [Off] to stop operation before uploading ordownloading data.2. Press [Main Menu] parameter 0-50 LCP Copy andpress [OK].3. Select [1] All to LCP to upload data to the LCP orselect [2] All from LCP to download data from theLCP.4. Press [OK]. A progress bar shows the uploading ordownloading progress.5. Press [Hand On] or [Auto On] to return to normaloperation.5.3.5 Changing Parameter SettingsParameter settings can be accessed and changed from theQuick Menu or from the Main Menu. The Quick Menu onlygives access to a limited number of parameters.1. Press [Quick Menu] or [Main Menu] on the LCP.2. Press [▲] [▼] to browse through the parametergroups, press [OK] to select a parameter group.3. Press [▲] [▼] to browse through the parameters,press [OK] to select a parameter.4. Press [▲] [▼] to change the value of a parametersetting.5. Press [◄] [►] to shift digit when a decimalparameter is in the editing state.6. Press [OK] to accept the change.7. Press either [Back] twice to enter Status, or press[Main Menu] once to enter the Main Menu.View changesQuick Menu Q5 - Changes Made lists all parameterschanged from default settings.• The list only shows parameters, which have beenchanged in the current edit set-up.• Parameters, which have been reset to defaultvalues, are not listed.• The message Empty indicates that no parametershave been changed.5.3.6 Restoring Default SettingsNOTICERisk of losing programming and monitoring records byrestoration of default settings. To provide a back-up,upload data to the LCP before initialisation.Restoring the default parameter settings is done by initiali-sation of the frequency converter. Initialisation is carriedout through parameter 14-22 Operation Mode(recommended) or manually.• Initialisation using parameter 14-22 OperationMode does not reset frequency converter settings,such as operating hours, serial communicationselections, personal menu settings, fault log,alarm log, and other monitoring functions.• Manual initialisation erases all motor,programming, localisation, and monitoring dataand restores factory default settings.Recommended initialisation procedure, viaparameter 14-22 Operation Mode1. Press [Main Menu] twice to access parameters.2. Scroll to parameter 14-22 Operation Mode andpress [OK].3. Scroll to [2] Initialisation and press [OK].4. Remove power to the unit and wait for thedisplay to turn off.5. Apply power to the unit.Default parameter settings are restored during start-up.This may take slightly longer than normal.6. Alarm 80 is displayed.7. Press [Reset] to return to operation mode.Manual initialisation procedure1. Remove power to the unit and wait for thedisplay to turn off.2. Press and hold [Status], [Main Menu], and [OK] atthe same time while applying power to the unit(approximately 5 s or until audible click and fanstarts).Factory default parameter settings are restored duringstart-up. This may take slightly longer than normal.Manual initialisation does not reset the following frequencyconverter information:• Parameter 15-00 Operating hours• Parameter 15-03 Power Up's• Parameter 15-04 Over Temp's• Parameter 15-05 Over Volt'sCommissioning Operating InstructionsMG16I302 Danfoss A/S © 04/2015 All rights reserved. 575 5