Cable length(ft [m])AC linevoltage[V]Rise time[μsec]Vpeak[kV]dU/dt[kV/μsec]120 [36] 400 0.232 0.950 3.534330 [100] 400 0.410 0.980 1.927500 [150] 400 0.430 0.970 1.860Table 9.27 Adjustable frequency drive, P22K, T4Cable length(ft [m])AC linevoltage[V]Rise time[μsec]Vpeak[kV]dU/dt[kV/μsec]50 [15] 400 0.271 1.000 3.100330 [100] 400 0.440 1.000 1.818500 [150] 400 0.520 0.990 1.510Table 9.28 Adjustable frequency drive, P30K, T4Cable length(ft [m])AC linevoltage[V]Rise time[μsec]Vpeak[kV]dU/dt[kV/μsec]16.4 [5] 480 0.270 1.276 3.781164 [50] 480 0.435 1.184 2.177330 [100] 480 0.840 1.188 1.131500 [150] 480 0.940 1.212 1.031Table 9.29 Adjustable frequency drive, P37K, T4Cable length(ft [m])AC linevoltage[V]Rise time[μsec]Vpeak[kV]dU/dt[kV/μsec]120 [36] 400 0.254 1.056 3.326164 [50] 400 0.465 1.048 1.803330 [100] 400 0.815 1.032 1.013500 [150] 400 0.890 1.016 0.913Table 9.30 Adjustable frequency drive, P45K, T4Cable length(ft [m])AC linevoltage[V]Rise time[μsec]Vpeak[kV]dU/dt[kV/μsec]33 [10] 400 0.350 0.932 2.130Table 9.31 Adjustable frequency drive, P55K, T4Cable length(ft [m])AC linevoltage[V]Rise time[μsec]Vpeak[kV]dU/dt[kV/μsec]16.4 [5] 480 0.371 1.170 2.466Table 9.32 Adjustable frequency drive, P75K, T4Cable length(ft [m])AC linevoltage[V]Rise time[μsec]Vpeak[kV]dU/dt[kV/μsec]16.4 [5] 400 0.364 1.030 2.264Table 9.33 Adjustable frequency drive, P90K, T4General Specifications and ... Design GuideMG11BC22 Danfoss A/S © Rev. 06/2014 All rights reserved. 1859 9