VLT ® FCM SeriesProgramming600 Operating data: Operating hours(OPERATING HOURS)Value:Unit: hours0.0 - 130,000.0Function:This parameter can be read out via the display or theserial communication port. The value cannot be reset.Description of choice:Indicates the number of hours in which the FCmotor has been switched on.The value is updated in the FC motor every hourand saved when the unit is turned off.601 Operating data: Hours run(RUNNING HOURS)Value:Unit: hours0.0 - 130,000.0Function:This parameter can be read out via the displayor the serial communication port. The value canbe reset via parameter 619.Description of choice:Indicates the number of hours in which the FC motorhas been in operation since reset in parameter 619.The value is updated in the FC motor every hourand saved when the unit is turned off.603 Operating data: Number of power-up’s(POWER UP’S)Value:Unit: number0 - 9999Function:This parameter can be read out via the displayor the serial communication port.Description of choice:States the number of power-ups of the supplyvoltage to the FC motor.604 Operating data: Number ofovertemperatures(OVER TEMP’S)Value:Unit: number0 - 9999Function:This parameter can be read out via the displayor the serial communication port.Description of choice:States the number of temperature faults therehas been on the FC motor.605 Operating data: Number of overvoltages(OVER VOLT’S)Value:Unit: number0 - 9999Function:This parameter can be read out via the displayor the serial communication port.Description of choice:States the number of overvoltages there hasbeen on the FC motor.615 Fault log: Error code(F.LOG: ERROR COD)Value:[Index XX - XXX]Function:Array type parameter. This parameter makes it possibleto see the reason why a trip occurs.10 log values are stored.The lowest log number (1) contains the latest/mostrecently saved data value; the highest log number(10) contains the oldest data value.For additional information, see chapter on "Warnings and alarms".Description of choice:Read out as a figure code between 1 and 37.✭ = factory setting. () = display text [] = value for use in communication via serial communication portMG.03.H3.02 - VLT is a registered Danfoss trademark 75