Parameter Overview*[2] 9600 Baud[3] 19200 Baud[4] 38400 Baud[5] 57600 Baud[6] 76800 Baud[7] 115200 Baud8-33 FC Port Parity*[0] Even Parity, 1 Stop Bit[1] Odd Parity, 1 Stop Bit[2] No Parity, 1 Stop Bit[3] No Parity, 2 Stop Bits8-35 Minimum Response Delay0.001 - 0.500s, * 0.0108-36 Max Response Delay0.100 - 10.000s, *5.0008-37 Max Inter-char delay0.025 - 0.025s, * 0.0258-5* Digital/Bus8-50 Coasting Select[0] Digital input[1] Bus[2] Logic AND*[3] Logic OR8-51 Quick Stop Select[0] Digital input[1] Bus[2] Logic AND*[3] Logic OR8-52 DC Brake Select[0] Digital input[1] Bus[2] Logic AND*[3] Logic OR8-53 Start Select[0] Digital input[1] Bus[2] Logic AND*[3] Logic OR8-54 Reversing Select[0] Digital input[1] Bus[2] Logic AND*[3] Logic OR8-55 Set-up Select[0] Digital input[1] Bus[2] Logic AND*[3] Logic OR8-56 Preset Reference Select[0] Digital input[1] Bus[2] Logic AND*[3] Logic OR8-7* Bacnet8-70 BACnet Device Instance0 - 0x400000UL* 18-72 MS/TP Maxmaster0 - 127, * 1278-73 MS/TP Max Info Frames1 - 65534, * 18-74 "I am" Service*[0] Send at power-up[1] Continuously8-75 Intialisation Password8-8* FC Port Diagnostics8-80 Bus Message Count0 - 65536, * 08-81 Bus Error Count0 - 65536, * 08-82 Slave Message Rcvd0 - 65536, * 08-83 Slave Error Count0 - 65536, * 08-84 Slave Message Sent0 - 65536, * 08-85 Slave Timeout Errors0 - 65536, * 08-88 Reset FC port Diagnostics*[0] Do not reset[1] Reset counter8-9* Bus Feedback8-94 Bus feedback 1-32768 - 32767, * 013-** Smart Logic13-0* SLC Settings13-00 SL Controller Mode*[0] Off[1] On13-01 Start Event[0] False[1] True[2] Running[3] In range[4] On reference[7] Out of current range[8] Below Ilow[9] Above Ihigh[16] Thermal warning[17] Mains out of range[18] Reversing[19] Warning[20] Alarm (trip)[21] Alarm (trip lock)[22] Comparator 0[23] Comparator 1[24] Comparator 2[25] Comparator 3[26] Logic rule 0[27] Logic rule 1[28] Logic rule 2[29] Logic rule 3[33] Digital input 18[34] Digital input 19[35] Digital input 27[36] Digital input 29*[39] Start command[40] Drive stopped[41] Reset trip[42] Auto reset trip[43] Key Ok[44] Key Reset[47] Key Up[48] Key Down[50] Comparator 4[51] Comparator 5[60] Logic rule 4[83] Broken belt13-02 Stop EventSee par. 13-02, *[40] Drive stopped13-03 Reset SLC*[0] Do not reset[1] Reset SLC13-1* Comparators13-10 Comparator Operand*[0] Disabled[1] Reference[2] Feedback[3] Motor speed[4] Motor current[6] Motor power[7] Motor voltage[8] DC-link voltage[12] Analog in 53[13] Analog in 54[20] Alarm number[30] Counter A[31] Counter B13-11 Comparator Operator[0] Less Than*[1] Approx. Equal[2] GreaterThan13-12 Comparator Value-9999.0 - 9999.0, * 0.013-2* Timers13-20 SL Controller Timer0.00 - 3600.00, * 0.0013-4* Logic Rules13-40 Logic Rule Boolean 1See par. 13-01, *[0] False13-41 Logic Rule Operator 1*[0] Disabled[1] AND[2] OR[3] AND NOT[4] OR NOT[5] NOT AND[6] NOT OR[7] NOT AND NOT[8] NOT OR NOT13-42 Logic Rule Boolean 2See par. 13-01, *[0] False13-43 Logic Rule Operator 2See par. 13-41, *[0] Disabled13-44 Logic Rule Boolean 3See par. 13-01, *[0] False13-5* States13-51 SL Controller EventSee par. 13-01, *[0] False13-52 SL Controller Action*[0] Disabled[1] No action[2] Select set-up 1[3] Select set-up 2[10] Select preset ref 0[11] Select preset ref 1[12] Select preset ref 2[13] Select preset ref 3[14] Select preset ref 4[15] Select preset ref 5[16] Select preset ref 6[17] Select preset ref 7[18] Select ramp 1[19] Select ramp 2[22] Run[23] Run reverse[24] Stop[25] Qstop[26] DC Brake[27] Coast[28] Freeze output[29] Start timer 0[30] Start timer 1[31] Start timer 2[32] Set digital out A low[33] Set digital out B low[34] Set digital out C low[35] Set digital out D low[38] Set digital out A high[39] Set digital out B high[40] Set digital out C high[41] Set digital out D high[60] Reset Counter A[61] Reset Counter B[70] Start timer 3[71] Start timer 4[72] Start timer 5[73] Start timer 6[74] Start timer 7[100] Reset Alarm14-** Special Functions14-0* Inverter Switching14-01 Switching Frequency[0] Ran3[1] Ran5[2] 2.0 kHz[3] 3.0 kHz[4] 4.0 kHzQuick Guide VLT HVAC Basic Drive FC 101 Quick GuideMG.18.A1.02 - VLT® is a registered Danfoss trademark 211 1