1.3.3 Mechanical DimensionsAabBC D130BB614.10Power (kW/Hp) Height (mm/inch) Width (mm/inch) Depth(mm/inch)Hole (mm)Frame IP class 3x200-240V 3 x 380-480V A A incl.DecouplingplateA B b C DH1 IP20 0.25-1.5 kW/0.33-2 Hp0.37-1.5kW/0.5-2Hp195/7.7 273/10.7 183/7.2 75/3 56/2.2 168/6.6 4.5H2 IP20 2.2 kW/3 Hp 2.2-4kW/3-5.4Hp227/8.4 303/11.9 212/8.3 90/3.5 65/2.6 190/7.5 5.5H3 IP20 3.7kW/5Hp 5.5-7.5kW/7.5-10Hp255/10 329/13 240/9.4 100/3.9 74/2.9 206/8.1 5.5H4 IP20 5.5-7,5kW/7.5-10Hp11-15kW/15-20Hp296/11.7 359/14.1 275/10.8 135/5.3 105/4.1 241/9.5 7H5 IP20 11kW/15Hp 18.5-22kW/25-30Hp334/13.1 402/15.8 314/12.4 150/5.9 120/4.7 255/10 7H6 IP20 30-45kW/40-60Hp518/20.4 595/23.4635/25495/19.5 239/31.5 200/7.9 242/9.5 8.5H7 IP20 55-75kW/100-120Hp550/21.7 630/24.8690/27.2521/20.5 313/12.3 270/10.6 335/13.2 8.5H8 IP20 90kW/120Hp660/26 800/31.5 631/24.8 375/14.8 330/13 335/13.2 8.5Table 1.1 Mechanical Dimensions1.3.4 Electrical Installation in GeneralAll cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copperconductors required, (75°C) recommended.Power (kW) Torque (Nm)Frame IP class 3 x 200-240V 3 x 380-480 Line Motor DCconnectionControlterminalsEarth RelayH1 IP20 0.25-1.5 0.37-1.5 1.4 0.8 0.8 0.5 3 0.5H2 IP20 2.2 2.2-4 1.4 0.8 0.8 0.5 3 0.5H3 IP20 3.7 5.5-7.5 1.4 0.8 0.8 0.5 3 0.5H4 IP20 5.5-7.5 11-15 1.2 1.2 1.2 0.5 3 0.5H5 IP20 11 18.5-22 1.2 1.2 1.2 0.5 3 0.5H6 IP20 30-45 4.5 4.5 - 0.5 3 0.5H7 IP20 55 10 10 - 0.5 3 0.5H7 IP20 75 14 14 - 0.5 3 0.5H8 IP20 90 14 14 - 0.5 3 0.5H8 IP20 90 24 24 - 0.5 3 0.5Table 1.2 Details of Tightening TorquesQuick Guide VLT HVAC Basic Drive FC 101 Quick Guide4 MG.18.A1.02 - VLT® is a registered Danfoss trademark11