8 General Specifications and Troubleshooting8.1 Mains Supply TablesMains supply 200 - 240 VAC - Normal overload 110% for 1 minuteFrequency converterTypical Shaft Output [kW]P1K11.1P1K51.5P2K22.2P3K03P3K73.7IP 20 / Chassis(A2+A3 may be converted to IP21 using a conversion kit. (Please seealso itemsMechanical mounting in Operating Instructions andIP 21/Type 1 Enclosure kit in the Design Guide.))A2 A2 A2 A3 A3IP 55 / NEMA 12 A5 A5 A5 A5 A5IP 66 / NEMA 12 A5 A5 A5 A5 A5Typical Shaft Output [HP] at 208 V 1.5 2.0 2.9 4.0 4.9Output currentContinuous(3 x 200-240 V ) [A] 6.6 7.5 10.6 12.5 16.7Intermittent(3 x 200-240 V ) [A] 7.3 8.3 11.7 13.8 18.4ContinuouskVA (208 V AC) [kVA] 2.38 2.70 3.82 4.50 6.00Max. cable size:(mains, motor, brake)[mm2 /AWG] 2) 4/10Max. input currentContinuous(3 x 200-240 V ) [A] 5.9 6.8 9.5 11.3 15.0Intermittent(3 x 200-240 V ) [A] 6.5 7.5 10.5 12.4 16.5Max. pre-fuses1) [A] 20 20 20 32 32EnvironmentEstimated power lossat rated max. load [W] 4) 63 82 116 155 185Weight enclosure IP20 [kg] 4.9 4.9 4.9 6.6 6.6Weight enclosure IP21 [kg] 5.5 5.5 5.5 7.5 7.5Weight enclosure IP55 [kg] 13.5 13.5 13.5 13.5 13.5Weight enclosure IP 66 [kg] 13.5 13.5 13.5 13.5 13.5Efficiency 3) 0.96 0.96 0.96 0.96 0.96Table 8.1: Mains Supply 200 - 240 VACVLT® HVAC Drive Design Guide 8 General Specifications and TroubleshootingMG.11.B9.02 - VLT® is a registered Danfoss trademark 1558